CMSX-...-C-U-F1-...
50
Festo – CMSX-...-C-U-F1-... – 1506a English
7.7.3
Performance of automatic initialization (Autoinit)
In automatic initialization, the CMSX automatically carries out an initialization run. The drive is moved
thereby!
Note
During initialization, the process valve is moved to the physical end positions.
Execute initialization only during the commissioning phase.
This is how you start automatic initialization:
1. Activate the compressed air supply.
2. Switch on the operating voltage. The CMSX then displays the initial position, e.g.:
−−−
0.0%
VP: 0.0%
3. Press the Set key for approx. 3 s. The CMSX then displays the first menu.
MENU
1 Sensor
4. Briefly press the Sub key. Then the CMSX shows the menu 6.
Alternatively, you can also press the Add key 5 times to switch from menu 1 to menu 6.
MENU
6 INIT
5. To open the menu, briefly press the Set key. The first command in the menu is then displayed.
*INITIA*
Autoinit
6. To start automatic initialization, hold down the Set and Add keys simultaneously for approx.
3 seconds. Initialization will then be started. The drive is moved.
Initialization takes a certain amount of time. The individual steps of initialization are shown on the
display (
è
AutoInit
24-- 1
...
AutoInit
24-- ...
...
AutoInit
24--22