Note
During initialization the process valve is moved to the end positions. As a rule, there
fore, initialization may only be performed during the commissioning phase – dependent
on the system.
Display
Description
MENU 6 INIT
Autoinit
Starts automatic initialization
1)
(
è
Here, the drive is moved into the end positions. Automatic initialization takes a
certain amount of time.
Userinit
Starts user-guided initialization
1)
. Here, the drive is moved into the end positions.
With user-guided initialization, each individual step of initialization is started by
pressing the Add button by hand.
Fcty Rst
Resets all current settings to the presettings valid from the plant (delivery
status
è
Sytm Rst
Resets all current settings to the individual presettings previously saved with
SET AS DEF.
SET AS DEF
Saves all current settings as individual presettings.
1)
In initialization, the positioner determines the swivel angle and a maximum positioning time. In doing so, it coordinates control of
the fast-switching valves with the direction of rotation of the potentiometer. VP and SP then behave synchronously.
Tab. 24
Initialization menu (6)
MENU
6 INIT
*INITIA*
Autoinit
Userinit
Fcty Rst
...
6
3
AutoInit
24-- 1
7
1
2
AutoInit
24-- ...
AutoInit
OK
1
2
1
Caution: Function is activated. The drive is
moved in initialization!
2
Automatic sequence of initialization
Fig. 34
Movement in the Initialization menu (6) – example AutoInit
Operation
Selection in the menu
Briefly press Add
1
Continue to the next selection
Briefly press Sub
2
Back to the previous selection