CMSX-...-C-U-F1-...
Festo – CMSX-...-C-U-F1-... – 1506a English
29
7.6.3
Basic menu level
After switching on the operating voltage supply the CMSX is automatically located in the initial position
of the basic menu level (
è
). In the initial position, it displays the following:
– The current setpoint position in percentage (in line 1 – SP stands for setpoint position)
– The current valve position in percent (in line 2 – VP stands for valve position).
The display of the initial position depends on the operating mode and the operating status of the
device.
Initial position
Display
1)
Meaning
Brief description
SP:50.0%
VP:50.1%
Automatic
operation;
Controller is
in operation
The CMSX is in automatic operation in the operating status
controller in operation (Running) and shows the analogue
specified setpoint position (SP) and the current valve position
(VP) in percent.
-->50.0%
VP:50.1%
Manual override;
controller is
in operation
The CMSX in manual override is in the operating status
controller in operation (Running) and shows the key-specified
setpoint position and the current valve position in percent.
***50.0%
VP:50.1%
Automatic or
manual override;
Control through
digital input
The CMSX is in automatic operation or manual override. But the
controller is inactive, since a control signal is present at the D-IN
control port. Dependent on the configuration, working ports of
the device can be pressurized or exhausted (
è
---50.0%
VP:50.1%
Automatic or
manual override;
controller is
stopped
The CMSX is in automatic operation or manual override in the
operating status controller stopped (Stopped) and shows the
setpoint position and the current valve position in percent.
1)
SP = setpoint position; VP = valve position; *** = digital control signal is present; --- = controller stopped; values here as an
example
Tab. 6
Display in the initial position – example
If the manual override is active, you can set the setpoint value in the initial position with the Add and
Sub keys (
è
Tab. 7).
Note
If the controller is in operation and no control signal is present at the control port, the
new setpoint value is effective immediately – even in manual override!
If the limit value (0 % or 100 %) is reached, the setpoint value jumps over to the minim
um or maximum setpoint value when the Add or Sub key is pressed again!
You can continue within the basic menu level by pressing the Set key (3) (
è
once, the current operating status (Running or Stopped) is displayed. There you can change the operat
ing status with immediate effect by pressing the Add or Sub key. After continuation again, the current
operating mode (Auto or Manual) is displayed. Here, too, you can change the current setting with the
Add or Sub key. The selected operating mode is taken over only after the Set key is pressed with con
tinuation into the initial position.