CMSX-...-C-U-F1-...
58
Festo – CMSX-...-C-U-F1-... – 1506a English
13
Technical data
CMSX-...-S-A1-C-U-F1-D-...
-A
-C
Sensing range in degrees
[°]
0 ... 100
Conforms to standard
VDI/VDE 3845 (Namur)
Protection against short circuit
yes
Measured variable
– CMSX-S
Rotation angle
– CMSX-SE
Rotation angle or stroke
Protection against polarity reversal
– For setpoint value
– For operating voltage connection
Display type
Backlit LCD
Setting options
Via display and keys
Type of process valve characteristic
curves
– Linear
– Equal percentage (1:25, 1:33, 1:50)
– Freely adjustable over 21 support points
Leakproof characteristics
Adjustable via SPMIN and SPMAX
Control range adaptation
Adjustable
Alarm for exceeding limit value
no
Active direction
Adjustable, rising/falling
Operating pressure
[bar]
3 ... 8
Setpoint value
[mA]
0 ... 20; 4 ... 20
[V]
0 ... 10
Safety instructions – behaviour in case of
voltage failure
Adjustable;
opening, closing
hold
Operating voltage range DC
[V DC]
21.6 ... 26.4
Max. load resistance of current output
[Ω]
500
Idle current
[mA]
100 ... 300
Max. current consumption
[A]
1
Max. output current
[mA]
500
Switching level
[V]
Signal 0:
5; Signal 1:
10
Max. current consumption of the digital
inputs at 24 V
[mA]
6
Size of the dead zone
[%]
0.5 ... 10
Operating medium
Compressed air to ISO 8573-1:2010 [7:4:4]
Note on the operating medium
Lubricated operation not possible
CE marking,
(Declaration of conformity
è
www.festo.com)
To EU EMC Directive
1)
Protection class - in mounted status
IP65
Ambient temperature
[°C]
-5 ...
60
1)
The product is intended for use in industrial environments. Outside of industrial environments, e.g. in commercial and mixed-resid
ential areas, actions to suppress interference may have to be taken.
Tab. 27
Technical data – part 1