6. Electrical installation
106
Festo.P.BE-CMMS-ST-G2-HW-EN
1008NH
6.4
Interfaces
6.4.1
I/O interface [X1]
Mode switching allows assignment of the [X1] interface more than once.
As a result, a maximum of four different I/O assignments can be selected.
Mode DIN9
DIN12
Table
Mode 0 – Positioning
0
0
Mode 1 – Jog mode
0
1
Mode 2 – Record linking
1
0
Mode 3 – Synchronisation
1
1
Table
6.1 Mode switching
Pin
Name
Value
Mode = 0 - Positioning
1
AGND
0 V
Screen for analogue signals
2
AIN0
±10 V
Setpoint input 0, differential, maximum 30 V input voltage
3 DIN10
Record
selection 4 (high active)
4
+VREF
+10 V ±4%
Reference output for setpoint potentiometer
5 Unassigned
6
GND24
Reference potential for digital inputs and outputs
7
DIN1
Record selection 1 (high active)
8
DIN3
Record selection 3 (high active)
9
DIN5
Controller enable (high active)
10
DIN7
Limit switch 1
11 DIN9
High-speed
input
12
DOUT1
24 V 100 mA Output freely programmable – Default: Motion complete (high active)
13
DOUT3
24 V 100 mA Output freely programmable – Default: Error (low active)
14
AGND
0 V
Reference potential for the analogue signals
15
DIN13
Ri = 20k
Stop input (low active)
16 DIN11
Record
selection 5 (high active)
17
AMON0
0...10 V ±4% Analogue monitor output 0
18
+ 24 V
24 V 100 mA 24 V supply carried out
19
DIN0
Record selection 0 (high active)
20
DIN2
Record selection 2 (high active)
21
DIN4
End stage enable (high active)
22
DIN6
Limit switch 0
23
DIN8
Start for the positioning procedure