59
SERIAL INTERFACE: RS485 MODBUS® RTU
Parameter/Description
Def Min Max U.M. Type
(*)
Decimal
Position Modbus
Modbus
HEX
R/W Notes/Meaning
Pump A evaporator status
0
1
D
0
1525
05F5
R
0 = off
1 = on
Pump B evaporator status
0
1
D
0
1526
05F6
R
Enabling pump A evaporator
1
0
1
D
0
1127
0467
R/W 0 = not enabled
1 = enabled
Enabling pump B evaporator
1
0
1
D
0
1128
0468
R/W
DAY of use pump A evaporator
0
32000
I
0
1152
0480
R
DAY of use pump B evaporator
0
32000
I
0
1153
0481
R
HOUR of use pump A evaporator
0
24
h
I
0
1154
0482
R
HOUR of use pump B evaporator
0
24
h
I
0
1155
0483
R
Heat recovery pump A status
0
1
D
0
1384
0568
R
Heat recovery pump B status
0
1
D
0
1385
0569
R
Enabling Heat recovery pump A
1
0
1
D
0
423
01°7 (a)
R/W 0 = off
1 = on
Enabling Heat recovery pump B
1
0
1
D
0
424
01°8 (a)
R/W
DAY of use Heat recovery pump A
0
32000
I
0
1160
0488
R
0 = not enabled
1 = enabled
DAY of use Heat recovery pump B
0
32000
I
0
1161
0489
R
HOUR of use Heat recovery pump A
0
24
h
I
0
1162
048A
R
HOUR of use Heat recovery pump B
0
24
h
I
0
1163
048B
R
ALARM Evaporator pump A unavailable
0
0
2
I
0
1294
050E
R
0 = not active
1 = active
2 = resettable
ALARM Evaporator pump B unavailable
0
0
2
I
0
1295
050F
R
ALARM Heat recovery pump A unavailable
0
0
2
I
0
1248
04E0
R
ALARM Heat recovery pump B unavailable
0
0
2
I
0
1249
04E1
R
ALARM Evaporator pump A thermal
0
0
2
I
0
1296
0510
R
ALARM Evaporator pump B thermal
0
0
2
I
0
1297
0511
R
ALARM Heat recovery pump A thermal protection
0
0
2
I
0
1250
04E2
R
ALARM Heat recovery pump B thermal protection
0
0
2
I
0
1251
04E3
R
MODBUS ® Address Table: Pumps Level
(*)
Type of variable/parameter:
A= Analog; D = Digital; I = Integer
Parameter/Description
Def Min
Max U.M. Type
(*)
Decimal
Position Modbus
Modbus
HEX
R/W Notes/Meaning
Circuit 1 status
0
4
I
0
1551
060F
R
0 = on
1 = alarm
2 = not used
3 = not used
4 = defrost
Circuit 2 status
0
4
I
0
1552
0610
R
Circuit 1 capacity
0
100
%
I
0
1543
0607
R
Circuit 2 capacity
0
100
%
I
0
1544
0608
R
Circuit 1 liquid temperature
-50.0 150.0
°C
A
1
1575
0627
R
Circuit 2 liquid temperature
-50.0 150.0
°C
A
1
1576
0628
R
Circuit 1 low pressure
-1.0
-30.0
bar
A
1
2332
091C
R
Only if installed
pressure
transducer
Circuit 2 low pressure
-1.0
-30.0
bar
A
1
2333
091D
R
Circuit 1 high pressure
-1.0
-50.0
bar
A
1
1559
0617
R
Circuit 2 high pressure
-1.0
-50.0
bar
A
1
1560
0618
R
Heat recovery circuit 1 status
0
1
I
0
1386
056A
R
0 = off ;
1 = on;
Heat recovery circuit 2 status
0
1
I
0
1387
056B
R
ALARM Circuit 1 low pressure
0
0
3
I
0
1270
04F6
R
0 = not active
1 = automatic
2 = resettable
3 = active
ALARM Circuit 2 low pressure
0
0
3
I
0
1271
04F7
R
ALARM Circuit 1 high pressure
0
0
2
I
0
1262
04EE
R
0 = not active
1 = active
2 = resettable
ALARM Circuit 2 high pressure
0
0
2
I
0
1263
04EF
R
ALARM Circuit 1 electronic expansion valve
0
0
2
I
0
1258
04EA
R
ALARM Circuit 2 electronic expansion valve
0
0
2
I
0
1259
04EB
R
ERROR Circuit 1 liquid probe
0
0
1
I
0
1339
053B
R
0 = active
1 = not active
ERROR Circuit 2 liquid probe
0
0
1
I
0
1340
053C
R
ERROR Circuit 1 low pressure transducer
0
0
1
I
0
1363
0553
R
0 = active
1 = not active
Only if installed
pressure
transducer
ERROR Circuit 2 low pressure transducer
0
0
1
I
0
1364
0554
R
ERROR Circuit 1 high pressure transducer
0
0
1
I
0
1327
052F
R
ERROR Circuit 2 high pressure transducer
0
0
1
I
0
1328
0530
R
Address Table MODBUS ®: Circuits Level
(*)