Electrical accessories
TP - Low and High pressure transducers (M).
Allow the display of the suction and discharge pressures of compressors. Their
presence activates an advanced defrost and condensation control logic and the ATC (Advanced Temperature Control) to prevent
high pressure alarm due to high external air temperature.
RAG- Storage tank electrical heater (F)
. Keeps water in storage tank above freezing point to avoid risk of icing during winter stops
it is activated together with plate heat exchanger electrical heater.
TAT- High Temperature Thermostat (M).
Two thermostats in series on compressors outlet pipes preserve operation not allowing
temperature to rise up than a specified non adjustable value.
CR- Remote control panel (F)
. Replies every control and visualization of the onboard control panel.
INT- Serial interface (M)
. Allows serial communication on RS485 by MODBUS protocol.
MTC - Magnetothermic switch (M).
Magnetothermic switch on all loads place of fuses.
SS - Soft Starter (M).
Soft starter on compressors allow to reduce to about a 60% nominal inrush current.
FLS - Flow switch (F).
Paddle flow switch on the water circuit to avoid the risk of freezing if the water flow is shut off for some reason.
RIF - Capacitors for power factor corrections (M).
Capacitors for power factor corrections increase power factor cos φ
(> 0.91)
and reduce power input.
CSF - Voltage monitor and sequence meter (M).
The device enables control of the correct sequence of power phases and the lack
of any phases.
KOP - Programmer clock (M).
Allows the unit to be turned on and off depending on the programmed time setting (up to 14 switching
actions can be programmed as required throughout the 7 days of the week).
DCC - Head pressure control (M).
(as standard for Low Noise unit AS and for eXtra Low Noise unit AX).
The device is made by 2 electrical drivers that, by means of phase cutting, control the fans speed rotation, with the scope of mantai-
ning the condensation pressure inside the correct operating limits.
Mechanical options
Special finned heat exchangers
• Coils with copper fins
• Coils with tin-coated copper fins
• Coils with aluminium fins with acrylic, epoxy or hydrofilic coating
.
Electrical options
Other power source voltage rating (contact our technical department).
ACCESSORIES AND OPTIONAL EQUIPMENT
Содержание RHA series
Страница 71: ...71 ...