33
GENERAL SPECIFICATIONS - VERSION wITH DESUPERHEATER (VD)
IP HEAT PUMP UNIT
(1):
The data refer to: Water temperature: evaporator inlet
:12°C
- evaporator outlet:
7°C,
Outdoor air temperature
35°C
.
The data refer to: Water temperature: recovery inlet :
40°C
- recovery outlet:
45°C.
Acoustic Version: AB (Standard Unit)
Recovery heat exchanger specifications
NOTE : THE HEATING CAPACITY RECOVERED BY THE DESUPERHEATER EXCLUSIVELY REFERS TO UNITS
OPERATING IN THE COOLING MODE.
(1):
Dati riferiti a: Temperatura acqua: ingresso evaporatore :
12°C
- uscita evaporatore:
7°C,
Temperatura aria esterna
35°C.
Dati riferiti a: Temperatura acqua: ingresso recupero:
40°C
- uscita recupero:
45°C.
Acoustic Version: AS (Low noise Unit)
Recovery heat exchanger specifications
NOTE : THE HEATING CAPACITY RECOVERED BY THE DESUPERHEATER EXCLUSIVELY REFERS TO UNITS
OPERATING IN THE COOLING MODE.
(1):
The data refer to: Water temperature: evaporator inlet
:12°C
- evaporator outlet:
7°C,
Outdoor air temperature
35°C
.
The data refer to: Water temperature: recovery inlet :
40°C
- recovery outlet:
45°C.
Acoustic Version: AX (Extra low noise Unit)
Recovery heat exchanger specifications
NOTE : THE HEATING CAPACITY RECOVERED BY THE DESUPERHEATER EXCLUSIVELY REFERS TO UNITS
OPERATING IN THE COOLING MODE.
MODEL
350.5
390.6
440.6
490.6
560.6
630.6
UM
Type of recovery exchanger
Brazed plates
-
Quantity
1
N°
Max. operating pressure on wet side
600
kPa
Total water content of recovery exchangers
1.3
1.3
1.3
1.3
1.3
1.3
l
Unit specification
Cooling capacity VD(1)
355
379
443
499
562
632
kW
Power input compressor VD (1)
101
109
126
145
161
183
kW
Total power input VD (1)
115
123
144
163
183
205
kW
EER VD (1)
3.09
3.08
3.08
3.06
3.07
3.08
-
Water flow rate VD (1)
16.9
18.1
21.2
23.9
26.8
30.2
l/s
Water pressure drop VD (1)
52
55
58
62
59
57
kPa
Recovered heating capacity (1)
85.2
90.7
106
120
135
152
kW
Recovered water flow rate (1)
4.07
4.33
5.06
5.73
6.45
7.26
l/s
Recovered water pressure drop (1)
23
26
24
30
29
36
kPa
MODEL
350.5
390.6
440.6
490.6
560.6
630.6
UM
Type of recovery exchanger
Brazed plates
-
Quantity
1
N°
Max. operating pressure on wet side
600
kPa
Total water content of recovery exchangers
3.8
3.8
3.8
3.8
3.8
3.8
l
Unit specification
Cooling capacity VD(1)
340
363
425
479
539
607
kW
Power input compressor VD (1)
109
117
136
156
174
198
kW
Total power input VD (1)
123
132
154
174
195
219
kW
EER VD (1)
2.76
2.75
2.76
2.75
2.76
2.77
-
Water flow rate VD (1)
16.2
17.3
20.3
22.9
25.7
29.0
l/s
Water pressure drop VD (1)
48
50
54
57
54
53
kPa
Recovered heating capacity (1)
85.2
90.7
107
120
135
152
kW
Recovered water flow rate (1)
4.07
4.33
5.09
5.72
6.45
7.25
l/s
Recovered water pressure drop (1)
23
26
24
30
29
36
kPa
MODEL
350.5
390.6
440.6
490.6
560.6
630.6
UM
Type of recovery exchanger
Brazed plates
-
Quantity
1
N°
Max. operating pressure on wet side
600
kPa
Total water content of recovery exchangers
3.8
3.8
3.8
3.8
3.8
3.8
l
Unit specification
Cooling capacity VD(1)
334
356
416
469
528
595
kW
Power input compressor VD (1)
112
120
140
160
178
204
kW
Total power input VD (1)
126
135
158
178
200
225
kW
EER VD (1)
2.65
2.64
2.63
2.63
2.64
2.64
-
Water flow rate VD (1)
16.0
17.0
19.9
22.4
25.2
28.4
l/s
Water pressure drop VD (1)
47
48
51
54
52
51
kPa
Recovered heating capacity (1)
85.2
90.7
106
120
135
152
kW
Recovered water flow rate (1)
4.07
4.33
5.06
5.73
6.45
7.26
l/s
Recovered water pressure drop (1)
23
26
24
30
29
36
kPa
Содержание RHA series