25
STANDARD PERFORMANCES - IP HEAT PUMP UNITS
Tw=
Outlet water temperature °C
kWf
= Cooling capacity (kW).
kWa
= Compressor power input (kW)
The standard performances refer to a 5°C temperature difference between the water entering and leaving the heat exchanger and to operation of the unit with all fans at
nominal or maximum speed. A 0.44 x 10
-4
m
2
K/W fouling factor has also been considered with the unit installed at zero meters above sea level (Pb = 1013mbar).
The performances are declared no considering any correction due to water flow rate and water side pressure drop (gross performance).
Performances in cooling mode - Low noise Unit AS
MOD.
Tw
OUTDOOR AIR TEMPERATURE (°C D.B.)
20
25
30
35
40
45 (1)
50 (1) (2)
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
kWf
kWa
350.5
5
373
78.6
348
90.4
329
99.6
309
110
288
121
278
123
255
133
6
384
79.3
358
91.3
339
101
318
111
296
122
286
124
262
134
7
395
80.1
368
92.2
348
102
327
112
304
123
294
125
270
135
8
406
81.0
379
93.2
358
103
336
113
313
125
302
126
-
-
9
417
81.8
389
94.2
368
104
346
114
321
126
310
128
-
-
10
428
82.6
400
95.1
378
105
355
116
330
127
319
129
-
-
11
439
83.5
410
96.0
388
106
364
117
338
129
327
130
-
-
12
451
84.3
421
97.0
398
107
374
118
348
130
336
131
-
-
390.6
5
398
84.9
372
97.7
352
108
330
119
307
131
297
132
272
143
6
409
85.7
382
98.6
361
109
339
120
316
132
305
133
280
144
7
421
86.6
393
99.6
372
110
349
121
325
133
314
135
288
146
8
433
87.5
404
101
382
111
359
122
334
135
323
136
-
-
9
445
88.4
416
102
393
112
369
124
343
136
331
137
-
-
10
457
89.3
427
103
403
113
379
125
352
138
340
139
-
-
11
469
90.2
437
104
414
114
388
126
361
139
349
140
-
-
12
481
91.0
449
105
425
115
399
127
371
140
358
142
-
-
440.6
5
467
98.2
436
113
412
125
387
137
360
151
347
153
319
166
6
480
99.2
448
114
423
126
397
139
370
153
357
155
328
167
7
494
100
461
115
436
127
409
140
381
154
367
156
337
169
8
508
101
474
117
448
128
421
142
391
156
377
158
-
-
9
522
102
487
118
461
130
432
143
402
158
388
160
-
-
10
536
103
500
119
473
131
444
144
413
159
398
161
-
-
11
549
104
513
120
485
132
455
146
423
161
408
163
-
-
12
564
105
527
121
498
134
467
147
435
162
419
164
-
-
490.6
5
526
113
491
130
464
143
436
158
406
174
391
176
359
190
6
541
114
505
131
477
145
448
159
417
176
402
177
369
192
7
557
115
519
133
491
146
461
161
429
177
414
179
380
194
8
572
116
534
134
505
148
474
163
441
179
425
181
-
-
9
588
118
549
135
519
149
487
164
453
181
437
183
-
-
10
604
119
563
137
533
151
500
166
465
183
449
185
-
-
11
619
120
578
138
546
152
513
168
477
185
460
186
-
-
12
636
121
594
139
561
154
527
169
490
187
473
188
-
-
560.6
5
591
126
552
145
522
159
490
176
456
193
440
196
404
212
6
608
127
567
146
536
161
503
177
468
195
452
197
415
213
7
625
128
584
147
552
162
518
179
482
197
465
199
427
216
8
643
129
600
149
568
164
533
181
496
199
479
202
-
-
9
661
131
617
150
583
166
547
183
509
201
492
204
-
-
10
678
132
633
152
599
167
562
185
523
203
505
206
-
-
11
696
133
649
153
614
169
576
186
536
205
518
208
-
-
12
715
135
667
155
631
171
592
188
551
207
532
210
-
-
630.6
5
667
143
622
165
588
181
552
200
514
221
495
223
455
241
6
685
144
639
166
605
183
567
202
528
223
509
225
468
243
7
705
146
658
168
622
185
584
204
543
225
524
227
481
246
8
725
148
677
170
640
187
601
206
559
227
539
230
-
-
9
745
149
695
171
658
189
617
208
574
230
554
232
-
-
10
765
151
714
173
675
191
633
210
589
232
568
234
-
-
11
784
152
732
175
692
193
650
212
604
234
583
237
-
-
12
806
153
752
177
711
195
667
215
621
236
599
239
-
-
(1) :
at these temperatures the fans are at maximum speed.
(2) :
ATC (Advanced Temperature Control) function may occur.
Содержание RHA series