8
INSTALLATION
PACKING AND STORING
CONTENT
Fig . 1
All machines are packed in cardboard boxes specific for each unit .
The indications required to correctly handle the appliance while storing and
installing it are written on the packing .
The storage temperature must be between
-25°C
and
55°C
.
Note:
Do not throw the packing away exteriors to avoid environmental pollution .
Once the place in which the unit is to be installed has been chosen (see the
relative sections) proceed as follows to unpack the two units:
Packagings contain the units as well as accessories and technical documentation for the use and installation . Check
that the following components are present .
In the indoor unit:
Description
Image
Qty
Notes
Remote control
1
The remote control is not
supplied with batteries
Unit fastening plate
1
Fix on the rear part of
the unit
Press-in plugs for unit fastening
and remote control holder
5-8
According to the model
Screws
5-8
According to the model
Manuals
1+1
User manual and
installation manual
Indoor unit (fig . 1):
1 .
Cut the two nylon straps .
2 .
Open the upper side of the packing .
3 .
Take the unit and lift it up until completely out of the packing .
4 .
Remove the side protections and the nylon wrapping .
INSTALLATION NOTES
1 .The air conditioner is not allowed to use in a room that has running fire (such as firesource, working coal gas ware,
operating heater) .
2 .It is not allowed to drill hole or burn the connection pipe .
3 .The air conditioner must be installed in a room that is larger than the minimum room area . The minimum room area
is shown on the nameplate or following table 1 .
4 .Leak test is a must after installation .
Refrigerant charge (kg)
≤1.2
1 .3
1 .4
1 .5
1 .6
1 .7
1 .8
1 .9
2 .0
Min room area m²
/
1 .6
1 .9
2 .1
2 .4
2 .8
3 .1
3 .4
3 .8