5.5 FLUE OR CHIMNEY
We will use a flue or chimney to be able to remove the gases that are produced in the boiler during combustion to the
outside.
The responsibility for the works carried out for the flue is from the installer, so FERLUX recommends that the
installation be carried out by qualified personnel (who are in possession of the installer’s card), which will be
asked to perform the checks relating to the smoke duct, air intake, etc. In addition, all the safety regulations provided
for by the specific legislation in force in the country where it is installed must be respected.
5.5.1 GENERAL FUNDAMENTALS
For the installation of the flue, the following points must be considered:
• The smoke evacuation system must be unique for each boiler
(smoke outlet evacuations in common
with other appliances are not allowed).
• The smoke evacuation route will always be as short as possible and always looking for maximum
verticality.
• The internal section of the smoke evacuation duct should be uniform and preferably circular. In the event
that we had a square or rectangular section, the edges should be rounded with a minimum radius of 20 mm,
the curves will be regular and without discontinuities, ensuring that the deviations of the path refarding the axis are
not greater than 45°.
• It is strictly forbidden to install valves or closures that may obstruct the passage of fumes.
• It is necessary to avoid horizontal sections of chimney, since this most likely will get it dirty and requires a
more frequent cleaning of the ducts, in the event that it is inevitable there will be a minimum of upward inclination
and “T” will be installed in the changes of direction to provide cleaning access without having to disassemble all
the installation. The installation must be carried out in such a way as to ensure regular cleaning without the need
to dismantle the entire flue.
• For the installation of the smoke duct, safety standards and minimum distances must be respected.
Cleaning
record
Maximum 2 m horizontal
with min 5% slope
Cleaning
record
Cleaning
record