It is advisable to support it on a level, firm and fire-resistant base, or baseboard.
For the correct combustion it is essential that the fuel is dry, so an adequate storage of it is recommended, which
will have to be at a safe distance from the boiler (at least 1 meter) or in a different room.
In no case should it be stored
behind the boiler.
It will have a drain and sump connected to the drainage network.
The boiler should not be installed in rooms or areas where flammable or explosive products can be stored.
The installation of the boiler must ensure that the hydraulic circuit incorporates the necessary safety measures against the
increase in temperature and water pressure.
Any deficiencies in the electrical installation must be repaired.
A DRAIN COCK WILL HAVE TO BE INSTALLED IN THE HEATING CIRCUIT, LOCATED AT THE LOWEST
POINT AND AS CLOSE AS POSSIBLE TO THE BOILER.
MIN 700 mm
MIN 1000 mm
MIN 1000 mm
MIN 500 mm
BOILER
ROOM
FIG. 5