NOTICE
Before connecting the device to the generator, check whether the equipment is in good
condition and whether the required power exceeds the limit of the generator. Then start the
generator and connect the device.
Make sure the device is turned off before connecting to the generator.
When using the generator with a pure inductive load, the pure inductive load cannot exceed the
rated power of the generator. The power can only run 40% to 75% of rated power on pure inductive
load.
Model
FGHI3500RS
Rated Power (W)
3000
Frequency
(
Hz
)
50
Power Factor
(
cosΦ
)
1.0
AC
Resistive Load 100%
0-3000W
Inductive Load 40%~75%
0-1200W~2250W
DC
100W(12V\8.3A)
Rated Power Output Conditions of the Generator
Altitude: 0 meter; Ambient temperature: 25
℃
; Relative humidity:30%
Only in the specified cooling and ambient temperature, the generator can be loaded to the rated
power. If the operating conditions do not meet the requirements of the standard, or the generator or
engine cooling is poor (in a limited area), then the generator power should be reduced.
Ambient temperature coefficient:
℃(
Relative humidity 30%
)
Altitude (m)
Ambient temperature (
℃
)
25
30
35
40
45
0
1
0.98
0.96
0.93
0.90
500
0.93
0.88
0.83
0.78
0.73
1000
0.87
0.82
0.77
0.72
0.67
2000
0.75
0.70
0.65
0.60
0.55
3000
0.64
0.59
0.54
0.49
0.44
4000
0.54
0.49
0.44
0.39
0.34
Note:
When the relative humidity is 60%, the ambient temperature improvement factor is C-0.01
When the relative humidity is 80%, the ambient temperature improvement factor is C-0.02
When the relative humidity is 90%, the ambient temperature improvement factor is C-0.03
When the relative humidity is 100%, the ambient temperature improvement factor is C-0.04
16