www.fedsig.com
Fault
Description
Upper Fan Fail
A fan-monitor I/O board upper fan has failed.
File Corrupt
A firmware or data file on disk has failed validation on the
controller.
File Missing
A firmware or data file on disk cannot be found on the controller.
Firmware Mismatch
The A and B controllers in a duplicated or high-integrity system
are not running identical firmware, or the controller and DSP
firmware versions are not compatible.
Flash Error
An I/O board or amplifier has encountered a flash memory failure.
Flash Read Timeout
An I/O board or amplifier cannot read its flash memory.
Gain Error Major
An amplifier’s output is below 50% of nominal gain.
Gain Error Minor
An amplifier’s output is 50-70% of nominal gain.
Hardware Not
Available
The controller configuration specifies hardware that does not
exist.
I2c Bus Failure
An I/O board or amplifier has an I
2
C bus failure.
I2c Init Failed
A beacon-monitor I/O board was unable to initialize its I
2
C bus.
I2c Transaction Failed
A beacon-monitor, isolated input, or monitored input I/O board
encountered a problem with its I
2
C bus.
Impedance Too High
An amplifier or ISMT speaker has measured an impedance above
the configured valid range.
Impedance Too Low
An amplifier or ISMT speaker has measured an impedance below
the configured valid range.
In Test Mode
An I/O board or amplifier has been put in test mode via its
console.
Input Overload
An amplifier input has exceeded the permitted signal level.
Inputs Defaulted
An unconfigured isolated or monitored input I/O board has started
and configured its inputs with the defaults.
Internal Config Error
An I/O board has encountered a configuration error.
Internal Failure
The controller cannot validate or load a system file or a recorded
message file.
Line Open
A monitored input I/O board input has detected an open circuit.
Line Short
A monitored input I/O board input has detected a short circuit.
Loop Broken
An amplifier speaker circuit loop has broken.
Lost Comms
The controller is no longer able to communicate with an I/O
board, virtual I/O board, amplifier, access panel, or peer
controller.
Network Audio Fault
The DSP has encountered a problem with the Dante
®
audio.
Network Config Fault
The controller is unable to load the netconfig.
Nor Flash Crc
The controller NOR flash has become corrupt.
Output Overload
An amplifier output has exceeded the permitted signal level.
Over Temp Major
An amplifier output has been shut down due to overheating.
Over Temp Minor
An amplifier output has had its power reduced due to overheating,
or a fan-monitor I/O board is reporting the rack is over-
temperature.
Pcp Node Id Mismatch An I/O board software address does not match its hardware
address.