MODEL F80A

FURNACE SIZING

The maximum hourly heat loss for each heated space shall
be calculated in accordance with the procedures described
in Manual J titled, "Load Calculation" published by the Air
Conditioning Contractors of America, or by any other
method which is suitable for local conditions, provided the
results obtained are in substantial agreement with, and not
less than those obtained using the procedure described in
their manual.

In Canada, the maximum hourly heat loss for each heated
space shall be calculated in accordance with the procedures
described in the manuals of the Heating, Refrigeration and
Air Conditioning Institute of Canada (HRAI), or by any other
method which is suitable for local conditions, provided the
results obtained are in substantial agreement with, and not
less than those obtained using the procedure described in
their manuals.

If the installation is a retrofit application, do not rely on the
capacity of the existing heating equipment as a method to
size the new furnace. Many of the heat transfer multiples
listed in earlier versions of load calculation manuals were
much higher than those listed in more recent editions. It is
possible that energy saving measures have been completed
since the installation of the existing furnace. This might
include additional insulation in the attic or walls, the
application of sprayed foam insulation, the addition of
storm windows and doors, weather stripping, caulking, etc.

Many of the older furnaces were equipped with large belt
drive blower systems, operating at low RPMs. If replacing an
existing furnace, be sure that the existing ductwork can
handle the amount of airflow necessary for a reasonable
temperature rise. Most older gas furnaces operated with a
system temperature rise of 70 - 100°F. This series furnace has
been designed for operation with a system temperature rise
(DT) of 35 - 65°F or 30 – 60°F depending on which model is
being installed. See Table 1A below. If the furnace selected
has an identical output capacity as the original furnace, a
substantial increase in system airflow will be required. See
Table 1B below.

TABLE 1A

FURNACE TEMPERATURE RISE

Fur nac e Mod 

Model

el Tem per atu re

Rise

35 – 65 F

30 – 60 F

35 – 65 F

30 – 60 F

35 – 65 F

30 – 60 F

30 – 65 F

TABLE 1B

TYPICAL AIR FLOW

CF M Re qu ired  for a

T of:

35 45 55 65 

35-2

50-3
70-3

70-4

85-3

85-4

100-3
100-4

100-5
115-5

35-2

50-3

70-3

70-4

85-3

85-4

100-4

100-5

115-5

737

574

469

397

1053

819

670

567

1433

1114

912

771

1433

1114

912

771

1791

1393

1140

964

1791

1393

1140

964

2107

1639

1341

1134

100-3

2107

1639

1341

1134

2107

1639

1341

1134

2423

1884

1542

1305

135-5

135-5

2844

2212

1810

1532

The equal friction chart, as published by ASHRAE and HRAI,
is the basis for the various air duct calculators available
through heating supply companies. 
NOTE: The return air system is equally as important as the
supply air system. An undersized return air system will
prevent sufficient quantities of air from reaching the supply
air system, properly sized or otherwise, and will
consequently reduce the service life of the furnace and its
components.

LOCATION of UNIT

GENERAL:

1. The furnace is not weatherized. Select a dry indoor

location.

2. Select a location where the furnace venting can be

routed between the furnace and the chimney or B-Vent
with a minimum of lengths and fittings. Be sure to
check that the proposed routing will meet code
requirements with respect to minimum clearances. 

3. Select a location as near as possible to the existing or

proposed duct system.

4. The furnace location must permit access for servicing,

and be within the clearance to combustibles guidelines
as marked on the appliance rating plate.

5. The furnace should be installed on a firm base when

installed in the upflow position. This is typically a
concrete floor if installing the furnace in a basement.

6. If the furnace is being installed so that the return air

will enter through the bottom, the perimeter of the
furnace must be properly supported.

7. When installed in the horizontal position, the furnace

may be supported from the bottom, or suspended.

8. When installed in the down flow position on a

combustible floor, subbase kit #30476 is required
(contact manufacturer for availability).

OTHER CONSIDERATIONS:

• This furnace is not to be used for temporary heating of

buildings or structures under construction.

• If this furnace is to be used with air conditioning and is

to be installed in an area over a finished ceiling or
living area, install a field fabricated auxiliary drain pan
under the furnace to protect that area from accidental
condensate spills. The auxiliary pan should be large
enough to collect accidentally spilled condensate from
the air conditioning evaporator coil assembly if
applicable. Follow local codes.

• These furnaces are approved for installation in attics,

alcoves, utility rooms, closets and crawlspaces. If this
furnace is to be installed in a utility room, be sure that
it is located in such a way as to allow access for
servicing or the removal of any other appliance, (hot
water heater, for example).

• If the furnace is to be installed in a garage, the burners

must be a minimum of 18 inches (460 mm) above the
floor.

• If the furnace is to be installed in a commercial (repair)

garage, the burners must be a minimum of 4.5 feet
(1375 mm) above the floor.

• The furnace must be protected from physical damage

by metal barriers or other acceptable means.

Existing ductwork should be assessed for its air handling
capabilities. For residential applications, the recommended
air velocity of a supply air trunk duct is 700 feet per minute
(fpm), and should not exceed 900 fpm. The recommended
air velocity of a supply air branch run is 600 fpm, and should
not exceed 900 fpm. These values are slightly lower for
flexible ducting. The recommended air velocity of a return
air trunk duct is 600 fpm, and should not exceed 700 fpm.
The recommended and maximum air velocity of a return air
branch is 600 fpm.

Содержание F80A

Страница 1: ...DIMENSIONS 5 DUCTWORK 6 DETERMING COMBUSTION AIR 7 FURNACE VENTING 8 GAS SUPPLY 12 CONVERSIONS 13 HIGH ALTITUDE AIRFLOW SPECIFICATION TABLES 14 ELECTRICAL SPECIFICATIONS 15 START UP PROCEDURES SEQUEN...

Страница 2: ...ated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furna...

Страница 3: ...sociation 1515 Wilson Boulevard Arlington VA 22209 703 841 8400 National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 9101 617 770 3000 Canadian Gas Association Suite 1 243 Consumer...

Страница 4: ...em An undersized return air system will prevent sufficient quantities of air from reaching the supply air system properly sized or otherwise and will consequently reduce the service life of the furnac...

Страница 5: ...pports so as not to interfere with accessing the burner and blower compartments The opening in the floor must provide adequate clearances to the combustible material According to the Clearances to Com...

Страница 6: ...E AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE...

Страница 7: ...UCING DEVICE SUCH AS A FIREPLACE INSERT STOVE ETC DOING SO MAY RESULT IN FIRE CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY LOSS OF LIFE OR PROPERTY DAMAGE CAUTION DO NOT USE THE REAR PANEL AS A...

Страница 8: ...gs one within 12 inches of the ceiling and the other within 12 inches of the floor The air openings must be sized based on whether the combustion and ventilation air is being taken from indoors or out...

Страница 9: ...NFPA 54 National Fuel Gas Code in the United States or B149 Natural Gas and Propane Installation Code in Canada and within the requirements of the codes of the local authority having jurisdiction Refe...

Страница 10: ...h joint to prevent sagging Horizontal segments must slope upward from the furnace to vent or chimney with a minimum 1 4 inch per foot When the vent tables from ANSI 223 1 NFPA 54 or B149 permit more t...

Страница 11: ...connector segments together with a minimum of three sheet metal screws per joint Secure the vent connector to the furnace collar with a minimum of three sheet metal screws Type B vent connectors do n...

Страница 12: ...EDICATED VENTING Figure 7 below shows a good method to permit dedicated venting making use of B Vent within a masonry chimney When using this method provide support for the B Vent IMPORTANT maintain a...

Страница 13: ...there is no blockage restriction leakage corrosion collapsed materials such as fallen bricks or any other deficiency that could lead to an unsafe condition 3 Insofar as practical duplicate winter oper...

Страница 14: ...ntity of dish detergent with water and daubing it onto the gas piping and connections PURGING GAS LINES NATURAL TO L P GAS This series furnace is manufactured as a natural gas sea level appliance It m...

Страница 15: ...5 mm 1 20 mm 135 2000 4500 121 500 97 200 1 90 mm 1 15 mm 0 2000 135 000 108 000 1 95 mm 1 20 mm 2000 3000 118 800 95 040 1 83 mm 1 13 mm 3000 4000 113 400 90 720 1 79 mm 1 10 mm 4000 5000 108 000 86...

Страница 16: ...ce requires a dedicated overcurrent device either a circuit breaker or a Type D time delay fuse It is permissible to connect furnace accessories such as humidifier transformers condensate pumps and el...

Страница 17: ...to the right hand side The junction box contains a BLACK wire to be connected with L1 hot a WHITE wire to be connected with L2 the Neutral and a GREEN wire to be connected to the ground Use good qual...

Страница 18: ...gin again at Step 4 above If the flame sensing signal is lost more than 5 times during a furnace cycle the gas valve will close and the ignition sequence goes into a 5 second postpurge the induced blo...

Страница 19: ...and the air filter or filters are in place determine if the airflow is correct 1 Insert a duct thermometer in the supply air duct The thermometer should be placed as close as practical to the furnace...

Страница 20: ...ower assembly to slide into blower rails Push blower assembly towards back of furnace ensuring blower assembly is correctly placed in blower rails Insert blower shroud on the front of the blower housi...

Страница 21: ...ture and drapes so that the supply air registers and return air grilles are unobstructed 5 If you have a perimeter duct system ideally the warm air should bathe the cold exterior walls Avoid the use o...

Страница 22: ...ft blue and not impinging on the heat exchanger CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Always verify proper ope...

Страница 23: ...TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY FLAME SENSE LOST MAIN VALVE CLOSES THERMOSTAT CALL FOR HEAT ENDS MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN...

Страница 24: ...23 MODEL F80A 50V51 250...

Страница 25: ...ne voltage to L1terminal of must be 120 volts with reference to furnace chassis 2 Furnace must be reliably connected to earth ground 3 Induced blower moving main burner flame away from the flame senso...

Страница 26: ...25 MODEL F80A R R 3 FACTORY SETTING...

Страница 27: ...O IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING LEAVE THE BUILDING IMMEDIATELY IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A P...

Страница 28: ...nside air from outdoors from an attic or crawl space If renovations are done be sure that air supply openings are not inadvertently covered over with insulation vapor barrier or similar construction m...

Страница 29: ...the next step 8 Gas valve Ensure that the Gas Valve Control is in the ON position see Figure 3 at right 9 Replace the burner access door ensuring that it is properly in place 10 Restore the electric...

Страница 30: ...the furnace All ductwork should be secured to the furnace and all ductwork should be solidly supported throughout the heating system The furnace should be well supported on a level floor or by the me...

Страница 31: ...operation points 5 and 9 will be ignored CAUTION THE FURNACE SHOULD BE OPERATED WITH ALL PANELS IN PLACE NEVER OPERATE THE FURNACE WITH THE BLOWER DOOR REMOVED EXCEPT FOR SERVICE PURPOSES WARNING ALWA...

Страница 32: ...o Warm Air Furnace products Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any...

Отзывы: