MODEL F80A

DANGER

READ, UNDERSTAND AND FOLLOW ALL INSTRUCTIONS
IN THIS SECTION. FAILURE TO PROPERLY VENT OR
SUPPLY COMBUSTION AIR TO THIS FURNACE CAN
CAUSE CARBON MONOXIDE POISONING, OR AN
EXPLOSION OR FIRE, RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.

WARNING

DO NOT ALLOW GAS PIPING TO BE ROUTED THROUGH
JOIST SPACES THAT ARE USED FOR RETURN AIR
PURPOSES. DO NOT USE JOIST SPACES FOR RETURN AIR
PURPOSES IF THE JOIST SPACE ALREADY CONTAINS
PLUMBING STACKS, CHIMNEY COMPONENTS, ETC.
UNLESS THE PORTION USED FOR RETURN AIR PURPOSES
CAN BE COMPLETELY ISOLATED FROM PORTIONS WITH
OTHER USAGES.

DANGER

THIS FURNACE AND ANY OTHER FUEL BURNING
APPLIANCE MUST BE PROVIDED WITH ENOUGH FRESH
AIR FOR PROPER COMBUSTION AND VENTILATION OF
THE FLUE GASES. MOST HOMES WILL REQUIRE THAT
OUTSIDE AIR BE BROUGHT TO THE FURNACE AREA.
FAILURE TO DO SO CAN CAUSE PERSONAL INJURY OR
DEATH FROM CARBON MONOXIDE POISONING.

CASE 1:

FURNACE LOCATED IN AN UNCONFINED SPACE

Unconfined space does not necessarily mean that
combustion and ventilation will not have to be introduced
from the outdoors, particularly in airtight homes. Refer to
the appropriate installation code requirements regarding
the minimum combustion air required for all fuel burning
appliances located within the unconfined area.

If the amount of combustion and ventilation air is
insufficient to properly operate the furnace and other fuel
burning appliances within the unconfined area, it will be
necessary to supply it from the outdoors based on the
criteria used when calculating the air supply for a confined
space.

NOTE: If planning to use the inside air of an unconfined
space, remember to test for proper furnace operation (as
well as other fuel burning appliances located within the
unconfined space) with respect to adequate combustion
and ventilation air with fireplace dampers open, clothes
dryer running, bathroom exhaust fans on, kitchen range
hood on, etc.

CASE 2:

FURNACE LOCATED IN A CONFINED SPACE

A confined space, (any space smaller than the minimums
discussed in CASE 1), must have two air openings one within
12 inches  of the ceiling and the other within 12 inches  of
the floor. The air openings must be sized based on whether
the combustion and ventilation air is being taken from
indoors or outdoors, the method outdoor air (if used) is
introduced, and taking into account any other fuel burning
appliances in the confined space.

If sufficient indoor combustion and ventilation air is
available for the furnace and all other fuel burning
appliances, even when clothes dryers, bathroom fans, range
hoods, etc. are running, size each opening according to the
appropriate installation codes. 

DETERMING COMBUSTION AIR

NOTE: If using grilles to cover the two openings, factor in
the free area of the grille. Typically, a grille will have a free
area approximately 50% of its nominal size. Consequently,
if the required opening is 10 inches x 10 inches  , it will have
to be doubled if using a sidewall grille with 50% free area.

IMPORTANT: If an exhaust fan, fireplace, clothes dryer or
any similar device is present in the indoor area from which
the combustion and ventilation air will be drawn, negative
pressure could be a problem if natural infiltration from the
outdoors does not match the rate at which air is exhausted.

CASE 3:

FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR
AIR FROM ATTIC OR CRAWL SPACE

In this circumstance, refer to the appropriate installation
code for the free area of the combustion and ventilation air
openings. If other fuel burning appliances are present, their
combustion air and ventilation air requirements must be
added to those of the furnace.

CASE 4:

FURNACE LOCATED IN A CONFINED SPACE, OUTDOOR
AIR DUCTED HORIZONTALLY

Similar to CASE 3, outdoor air for combustion and
ventilation may be drawn through horizontal ducting.
Consult the appropriate installation code for the free area
for openings. If other fuel burning appliances are present,
their combustion air and ventilation air requirements must
be added to those of the furnace.

IMPORTANT: The outdoor grilles must be installed in a
location where they will not be obstructed in any manner.

IMPORTANT: If grilles are used on the outside wall, they
must be sized properly. Most sidewall grilles have only 50%
free area, so the grill size opening must be twice the size of
the free air opening requirement.

Содержание F80A

Страница 1: ...DIMENSIONS 5 DUCTWORK 6 DETERMING COMBUSTION AIR 7 FURNACE VENTING 8 GAS SUPPLY 12 CONVERSIONS 13 HIGH ALTITUDE AIRFLOW SPECIFICATION TABLES 14 ELECTRICAL SPECIFICATIONS 15 START UP PROCEDURES SEQUEN...

Страница 2: ...ated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furna...

Страница 3: ...sociation 1515 Wilson Boulevard Arlington VA 22209 703 841 8400 National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 9101 617 770 3000 Canadian Gas Association Suite 1 243 Consumer...

Страница 4: ...em An undersized return air system will prevent sufficient quantities of air from reaching the supply air system properly sized or otherwise and will consequently reduce the service life of the furnac...

Страница 5: ...pports so as not to interfere with accessing the burner and blower compartments The opening in the floor must provide adequate clearances to the combustible material According to the Clearances to Com...

Страница 6: ...E AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE...

Страница 7: ...UCING DEVICE SUCH AS A FIREPLACE INSERT STOVE ETC DOING SO MAY RESULT IN FIRE CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY LOSS OF LIFE OR PROPERTY DAMAGE CAUTION DO NOT USE THE REAR PANEL AS A...

Страница 8: ...gs one within 12 inches of the ceiling and the other within 12 inches of the floor The air openings must be sized based on whether the combustion and ventilation air is being taken from indoors or out...

Страница 9: ...NFPA 54 National Fuel Gas Code in the United States or B149 Natural Gas and Propane Installation Code in Canada and within the requirements of the codes of the local authority having jurisdiction Refe...

Страница 10: ...h joint to prevent sagging Horizontal segments must slope upward from the furnace to vent or chimney with a minimum 1 4 inch per foot When the vent tables from ANSI 223 1 NFPA 54 or B149 permit more t...

Страница 11: ...connector segments together with a minimum of three sheet metal screws per joint Secure the vent connector to the furnace collar with a minimum of three sheet metal screws Type B vent connectors do n...

Страница 12: ...EDICATED VENTING Figure 7 below shows a good method to permit dedicated venting making use of B Vent within a masonry chimney When using this method provide support for the B Vent IMPORTANT maintain a...

Страница 13: ...there is no blockage restriction leakage corrosion collapsed materials such as fallen bricks or any other deficiency that could lead to an unsafe condition 3 Insofar as practical duplicate winter oper...

Страница 14: ...ntity of dish detergent with water and daubing it onto the gas piping and connections PURGING GAS LINES NATURAL TO L P GAS This series furnace is manufactured as a natural gas sea level appliance It m...

Страница 15: ...5 mm 1 20 mm 135 2000 4500 121 500 97 200 1 90 mm 1 15 mm 0 2000 135 000 108 000 1 95 mm 1 20 mm 2000 3000 118 800 95 040 1 83 mm 1 13 mm 3000 4000 113 400 90 720 1 79 mm 1 10 mm 4000 5000 108 000 86...

Страница 16: ...ce requires a dedicated overcurrent device either a circuit breaker or a Type D time delay fuse It is permissible to connect furnace accessories such as humidifier transformers condensate pumps and el...

Страница 17: ...to the right hand side The junction box contains a BLACK wire to be connected with L1 hot a WHITE wire to be connected with L2 the Neutral and a GREEN wire to be connected to the ground Use good qual...

Страница 18: ...gin again at Step 4 above If the flame sensing signal is lost more than 5 times during a furnace cycle the gas valve will close and the ignition sequence goes into a 5 second postpurge the induced blo...

Страница 19: ...and the air filter or filters are in place determine if the airflow is correct 1 Insert a duct thermometer in the supply air duct The thermometer should be placed as close as practical to the furnace...

Страница 20: ...ower assembly to slide into blower rails Push blower assembly towards back of furnace ensuring blower assembly is correctly placed in blower rails Insert blower shroud on the front of the blower housi...

Страница 21: ...ture and drapes so that the supply air registers and return air grilles are unobstructed 5 If you have a perimeter duct system ideally the warm air should bathe the cold exterior walls Avoid the use o...

Страница 22: ...ft blue and not impinging on the heat exchanger CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Always verify proper ope...

Страница 23: ...TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY FLAME SENSE LOST MAIN VALVE CLOSES THERMOSTAT CALL FOR HEAT ENDS MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN...

Страница 24: ...23 MODEL F80A 50V51 250...

Страница 25: ...ne voltage to L1terminal of must be 120 volts with reference to furnace chassis 2 Furnace must be reliably connected to earth ground 3 Induced blower moving main burner flame away from the flame senso...

Страница 26: ...25 MODEL F80A R R 3 FACTORY SETTING...

Страница 27: ...O IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING LEAVE THE BUILDING IMMEDIATELY IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A P...

Страница 28: ...nside air from outdoors from an attic or crawl space If renovations are done be sure that air supply openings are not inadvertently covered over with insulation vapor barrier or similar construction m...

Страница 29: ...the next step 8 Gas valve Ensure that the Gas Valve Control is in the ON position see Figure 3 at right 9 Replace the burner access door ensuring that it is properly in place 10 Restore the electric...

Страница 30: ...the furnace All ductwork should be secured to the furnace and all ductwork should be solidly supported throughout the heating system The furnace should be well supported on a level floor or by the me...

Страница 31: ...operation points 5 and 9 will be ignored CAUTION THE FURNACE SHOULD BE OPERATED WITH ALL PANELS IN PLACE NEVER OPERATE THE FURNACE WITH THE BLOWER DOOR REMOVED EXCEPT FOR SERVICE PURPOSES WARNING ALWA...

Страница 32: ...o Warm Air Furnace products Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any...

Отзывы: