background image

2

WARM AIR FURNACE

DANGER

WHAT TO DO IF YOU SMELL GAS:

• DO NOT TRY TO LIGHT ANY APPLIANCE

• DO NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT

USE ANY PHONE IN YOUR BUILDING

• IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A

NEIGHBOR’S PHONE, OR A CELLULAR PHONE FROM A
LOCATION WELL AWAY FROM THE BUILDING.
FOLLOW THE GAS SUPPLIER’S INSTRUCTIONS.

• IF YOU CANNOT REACH YOUR GAS SUPPLIER, CALL

THE FIRE DEPARTMENT

• DO NOT ENTER THE BUILDING UNTIL AUTHORIZED TO

DO SO BY THE GAS SUPPLIER OR THE FIRE
DEPARTMENT

IMPROPER INSTALLATION, OPERATION, ADJUSTMENT,
ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE
INJURY, PROPERTY DAMAGE OR LOSS OF LIFE. REFER TO
THIS MANUAL FOR PROPER INSTALLATION, OPERATION,
SERVICE, AND MAINTENANCE INSTRUCTIONS.

A QUALIFIED INSTALLER, SERVICE AGENCY OR
THE GAS SUPPLIER MUST PERFORM
INSTALLATION AND SERVICE.

DO NOT DESTROY THIS MANUAL

PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE
FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.

CODES:

This furnace must be installed:

• In accordance with all local codes, bylaws and

regulations by those authorities having jurisdiction

• In the United States, this furnace must be installed in

accordance with the current ANSI Z223.1 (NFPA 54)
National Fuel Gas Code

• In Canada, this furnace must be installed in

accordance with the current CAN/CGA -B149
Installation Code for Fuel Burning Appliances

Electrical connections must be made in accordance
with:

• Any applicable local codes, bylaws and regulations

• Canada: current edition of CAN/CSA C22.1, Canadian

Electrical Code (Part 1)

• United States: current edition of ANSI/NFPA 70,

National Electrical Code

Codes and additional information may be obtained
from:

American Gas Association

1515 Wilson Boulevard

Arlington, VA, 22209

703-841-8400

National Fire Protection Association

1 Batterymarch Park

Quincy, MA, 02269-9101

617-770-3000 

Canadian Gas Association

Suite 1, 243 Consumers Road

North York, ON, M2J 5E3

416-498-1994

WARNING

THE EXHAUST GASES FROM THIS FURNACE CONTAIN
CHEMICALS, WHICH ON SOME OCCASIONS MAY
INCLUDE CARBON MONOXIDE (CO). CARBON
MONOXIDE IS AN ODORLESS, TASTELESS, CLEAR
COLORLESS GAS, WHICH IS HIGHLY TOXIC. EVEN LOW
CONCENTRATIONS ARE SUSPECTED OF CAUSING BIRTH
DEFECTS AND OTHER REPRODUCTIVE HARM.

UL AND CUL RECOGNIZED CO DETECTORS ARE
RECOMMENDED FOR ALL BUILDINGS EQUIPPED WITH
FOSSIL FUEL BURNING APPLIANCES. ALL CO DETECTORS
SHOULD BE INSTALLED IN ACCORDANCE WITH THEIR
MANUFACTURER’S INSTRUCTIONS AND APPLICABLE
LOCAL BUILDING CODES.

WARNING

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO
QUALIFIED SERVICE PERSONNEL FOR PROPER
INSTALLATION, ADJUSTMENT AND OPERATION OF THIS
FURNACE. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION.
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT
IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR
MAINTENANCE, POSSIBLY RESULTING IN FIRE,
ELECTRICAL SHOCK, CARBON MONOXIDE POISONING,
EXPLOSION, PROPERTY DAMAGE, PERSONAL INJURY OR
DEATH.

DO NOT STORE OR USE GASOLINE OR OTHER
FLAMMABLE VAPORS AND LIQUIDS, OR OTHER
COMBUSTIBLE MATERIALS IN THE VICINITY OF THIS OR
ANY OTHER APPLIANCE.

DANGER

WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL
GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND
IGNITION SOURCE ARE LOCATED NO LESS THAN 18
INCHES ABOVE THE FLOOR TO PREVENT THE RISK OF
IGNITING FLAMMABLE VAPORS WHICH MAY BE
PRESENT IN THE GARAGE.

THE FURNACE MUST BE LOCATED OR PROTECTED TO
AVOID PHYSICAL DAMAGE BY VEHICLES.

FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE
OR EXPLOSION, RESULTING IN PROPERTY DAMAGE,
PERSONAL INJURY OR LOSS OF LIFE.

Содержание F80A

Страница 1: ...DIMENSIONS 5 DUCTWORK 6 DETERMING COMBUSTION AIR 7 FURNACE VENTING 8 GAS SUPPLY 12 CONVERSIONS 13 HIGH ALTITUDE AIRFLOW SPECIFICATION TABLES 14 ELECTRICAL SPECIFICATIONS 15 START UP PROCEDURES SEQUEN...

Страница 2: ...ated by the furnace to areas outside the space containing the furnace the return air shall also be handled by duct s sealed to the furnace casing and terminating outside the space containing the furna...

Страница 3: ...sociation 1515 Wilson Boulevard Arlington VA 22209 703 841 8400 National Fire Protection Association 1 Batterymarch Park Quincy MA 02269 9101 617 770 3000 Canadian Gas Association Suite 1 243 Consumer...

Страница 4: ...em An undersized return air system will prevent sufficient quantities of air from reaching the supply air system properly sized or otherwise and will consequently reduce the service life of the furnac...

Страница 5: ...pports so as not to interfere with accessing the burner and blower compartments The opening in the floor must provide adequate clearances to the combustible material According to the Clearances to Com...

Страница 6: ...E AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE...

Страница 7: ...UCING DEVICE SUCH AS A FIREPLACE INSERT STOVE ETC DOING SO MAY RESULT IN FIRE CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY LOSS OF LIFE OR PROPERTY DAMAGE CAUTION DO NOT USE THE REAR PANEL AS A...

Страница 8: ...gs one within 12 inches of the ceiling and the other within 12 inches of the floor The air openings must be sized based on whether the combustion and ventilation air is being taken from indoors or out...

Страница 9: ...NFPA 54 National Fuel Gas Code in the United States or B149 Natural Gas and Propane Installation Code in Canada and within the requirements of the codes of the local authority having jurisdiction Refe...

Страница 10: ...h joint to prevent sagging Horizontal segments must slope upward from the furnace to vent or chimney with a minimum 1 4 inch per foot When the vent tables from ANSI 223 1 NFPA 54 or B149 permit more t...

Страница 11: ...connector segments together with a minimum of three sheet metal screws per joint Secure the vent connector to the furnace collar with a minimum of three sheet metal screws Type B vent connectors do n...

Страница 12: ...EDICATED VENTING Figure 7 below shows a good method to permit dedicated venting making use of B Vent within a masonry chimney When using this method provide support for the B Vent IMPORTANT maintain a...

Страница 13: ...there is no blockage restriction leakage corrosion collapsed materials such as fallen bricks or any other deficiency that could lead to an unsafe condition 3 Insofar as practical duplicate winter oper...

Страница 14: ...ntity of dish detergent with water and daubing it onto the gas piping and connections PURGING GAS LINES NATURAL TO L P GAS This series furnace is manufactured as a natural gas sea level appliance It m...

Страница 15: ...5 mm 1 20 mm 135 2000 4500 121 500 97 200 1 90 mm 1 15 mm 0 2000 135 000 108 000 1 95 mm 1 20 mm 2000 3000 118 800 95 040 1 83 mm 1 13 mm 3000 4000 113 400 90 720 1 79 mm 1 10 mm 4000 5000 108 000 86...

Страница 16: ...ce requires a dedicated overcurrent device either a circuit breaker or a Type D time delay fuse It is permissible to connect furnace accessories such as humidifier transformers condensate pumps and el...

Страница 17: ...to the right hand side The junction box contains a BLACK wire to be connected with L1 hot a WHITE wire to be connected with L2 the Neutral and a GREEN wire to be connected to the ground Use good qual...

Страница 18: ...gin again at Step 4 above If the flame sensing signal is lost more than 5 times during a furnace cycle the gas valve will close and the ignition sequence goes into a 5 second postpurge the induced blo...

Страница 19: ...and the air filter or filters are in place determine if the airflow is correct 1 Insert a duct thermometer in the supply air duct The thermometer should be placed as close as practical to the furnace...

Страница 20: ...ower assembly to slide into blower rails Push blower assembly towards back of furnace ensuring blower assembly is correctly placed in blower rails Insert blower shroud on the front of the blower housi...

Страница 21: ...ture and drapes so that the supply air registers and return air grilles are unobstructed 5 If you have a perimeter duct system ideally the warm air should bathe the cold exterior walls Avoid the use o...

Страница 22: ...ft blue and not impinging on the heat exchanger CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Always verify proper ope...

Страница 23: ...TRIAL FOR IGNITION CIRCULATING AIR FAN ON AFTER DELAY FLAME SENSE LOST MAIN VALVE CLOSES THERMOSTAT CALL FOR HEAT ENDS MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN...

Страница 24: ...23 MODEL F80A 50V51 250...

Страница 25: ...ne voltage to L1terminal of must be 120 volts with reference to furnace chassis 2 Furnace must be reliably connected to earth ground 3 Induced blower moving main burner flame away from the flame senso...

Страница 26: ...25 MODEL F80A R R 3 FACTORY SETTING...

Страница 27: ...O IF YOU SMELL GAS DO NOT TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRICAL SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING LEAVE THE BUILDING IMMEDIATELY IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A P...

Страница 28: ...nside air from outdoors from an attic or crawl space If renovations are done be sure that air supply openings are not inadvertently covered over with insulation vapor barrier or similar construction m...

Страница 29: ...the next step 8 Gas valve Ensure that the Gas Valve Control is in the ON position see Figure 3 at right 9 Replace the burner access door ensuring that it is properly in place 10 Restore the electric...

Страница 30: ...the furnace All ductwork should be secured to the furnace and all ductwork should be solidly supported throughout the heating system The furnace should be well supported on a level floor or by the me...

Страница 31: ...operation points 5 and 9 will be ignored CAUTION THE FURNACE SHOULD BE OPERATED WITH ALL PANELS IN PLACE NEVER OPERATE THE FURNACE WITH THE BLOWER DOOR REMOVED EXCEPT FOR SERVICE PURPOSES WARNING ALWA...

Страница 32: ...o Warm Air Furnace products Illustrations cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any...

Отзывы: