![FE FSH Скачать руководство пользователя страница 63](http://html1.mh-extra.com/html/fe/fsh/fsh_instruction-manual_3753975063.webp)
INF-TN1FSH-E
- 55 -
4.4.4.2. Output limit
Description
The upper limit and the lower limit of analog output can be set within the range from 0.8 mA to 23.2 mA (
−
20% to
120%).
Analog output
20mA
23.2mA
4mA
0%
0.8mA
-20%
100% 120%
Lower limit
Upper limit
Flow rate
Operation
(example)
Lower limit:
−
10% (2.4 mA), upper limit: 110% (21.6 mA)
Key operation
Description
Display
FUNC RANGE
Display RANGE UNIT.
RANGE UNIT
m
3
/h
"
or
#
Select “OUTPUT LIMIT Lo.”
OUTPUT LIMIT Lo.
20%
ENTER 1 0 ENTER
Enter numeric value enter mode, enter “10”
using ten keys, and press ENTER.
OUTPUT LIMIT Lo.
10%
#
Select “OUTPUT LIMIT Hi.”
OUTPUT LIMIT Hi.
120%
ENTER 1 1 0 ENTER
Enter numeric value enter mode, enter
“110” using ten keys, and press ENTER.
OUTPUT LIMIT Hi.
110%
ESC
Display the measurement, reflecting the
setting.
(Measurement display screen)