INF-TN1FSH-E
- 53 -
*3) Maximum measurement range in hybrid mode
In the case of pulse Doppler method, the measurable range varies depending on the piping specifications and the
type of sensors used. If the measurement is to be made by hybrid method, set the full scale within the range that
does not exceed the measurement range. If the full scale exceeds the measurement range, select the time difference
method for measurement. After selecting the piping specifications and the sensor type, check the measurement
range within the maximum measurement data information range. See “6.1.2.3.” for details of checking.
The following table lists the maximum range in the case where stainless steel is selected as piping material,
Schedule 20S as nominal wall thickness, and water as fluid to be measured.
(Example)
<Maximum measurable flow velocity>
<Maximum measurable flow rate>
Unit: m/s
Unit: m
3
/h
Diameter FSW12
FSW21 FSW40
FSW50
FSW12
FSW21 FSW40 FSW50
40A
6.56
33.6
50A
6.52
52.7
65A
5.31
72.1
80A
4.65
86.5
90A
4.12
102
100A
3.69
7.25 118
231
125A
3.08
6.08 147
289
150A
2.63
5.20 179
354
200A
2.04
4.05
7.77 239
474
908
250A 3.30
6.38
604
1168
300A 2.78
5.41
735
1428
350A 2.51
4.90
820
1598
400A 2.20
4.31
951
1858
450A
3.84
2118
500A
3.48
3.48
2358
2358
550A
3.17
2618
600A
2.91
2879
650A
2.71
3096
700A
2.52
3357
750A
2.35
3618
800A
2.21
3879
850A
2.08
4140
900A
1.97
4400
1000A
1.77
4902
Operation
(example)
When selecting bi-directional for range, 100 m
3
/h for full scale 1,
−
100 m
3
/h for full scale 2, and 5%
for hysteresis
Key operation
Description
Display
FUNC RANGE
Display RANGE UNIT.
RANGE UNIT
m/s
ENTER
"
or
#
ENTER
Enter select/enter mode, select “m
3
/h,” and
press ENTER.
RANGE UNIT
m
3
/h
#
Select “RANGE TYPE”
RANGE TYPE
SINGLE
ENTER
"
or
#
ENTER
Enter select/enter mode, select “BI-DIR,”
and press ENTER.
RANGE TYPE
BI-DIR
#
Select “FULL SCALE 1”
FULL SCALE 1
56.32 m
3
/h
ENTER 1 0 0 ENTER
Enter numeric value enter mode, enter
“100” using ten keys, and press ENTER.
FULL SCALE 1
100.00 m
3
/h