Trace
36
4
Trace
The trace function allows recording up to 4 parameters of the controller. A trigger source is
available for this in the object dictionary. This allows selection of a maximum of 4 signal
sources. Two different types of recording are available:
Trace recorder: The parameter values are written to an internal buffer and can then be
read (see chap. 4.1, p. 36).
Trace logger: On request the parameter values are requested and read continuously
(see chap. 4.2, p. 39).
4.1
Trace recorder
The configuration and reading of data with the trace recorder is performed via the SDO.
The trace recorder is configured using the object 0x2370 in the OD.
The recorded data are read using the segmented SDO upload protocol. The object 0x2371 is
available in the OD for this purpose (see chap. 4.1.2, p. 38).
4.1.1
Trace settings
The object 0x2370 is available for configuration of the trace recorder. The data sources to
be recorded, the buffer size, the resolution and the trigger conditions can be set here.
Tab. 15: Trace Configuration (0x2370)
The FAULHABER Motion Manager provides a user-friendly means of setting and evalu-
ating the trace functions.
Index
Subindex Name
Type Attr.
Default value
Meaning
0x2370
0x00
Number of
Entries
U8
ro
10
Number of object entries
0x01
Trigger Source
U32
wo
0
Trigger source
0x02
Trigger Thresh-
old
S32
rw
0
Trigger threshold
0x03
Trigger Delay
Offset
S16
rw
0
Trigger delay
0x04
Trigger Mode
U16
rw
0
Trigger mode
0x05
Buffer Length
U16
rw
100
Buffer length
0x06
Sample Time
U8
rw
1
Recording sampling rate
1: in every sampling step
0x07
Trace Source of
Channel 1
U32
wo
0
Trace source of channel 1
0x08
Trace Source of
Channel 2
U32
wo
0
Trace source of channel 2
0x09
Trace Source of
Channel 3
U32
wo
0
Trace source of channel 3
0x0A
Trace Source of
Channel 4
U32
wo
0
Trace source of channel 4