FNet
+ -
CONNECTION I/O NETWORK
(control computer and I/O Network modules)
NEVER cut the
backbone cable.
Remove the
insulation only.
CONNECTION FNet
(control computers and PCs)
I/O Net
I/O-Net
FNet
FNet
The order of I/O network
modules is not important.
The order of systems
is not important.
Polarity of FNet
is not important.
(control computer)
Terminal
resistor
120
Ω
.
Terminal
resistor
120
Ω
.
PC with Network
card (and built-in
terminal resistor)
(I/O Network module)
(I/O Network module)
(I/O Network module)
(Control computer)
Terminal
resistor
120
Ω
.
WIRING OF I/O NETWORK AND FNET
:
1)
Phone cable (unshielded) 2 wire (twisted pair) + a single wire
(2x2x0.5mm + 1x0.5mm). One wire pair will not be used.
or
2) Unshielded 2 wire twisted pair (1x2x0.5mm or 1x2x0.8mm)
Max. length of both networks: wire: ø0,5mm --> 900m.
wire: ø0,8mm --> 1300m.
Connect Fancom equipment according to the prevailing
standards of the local electricity company.
The first and last
I/O Network module
must be terminated
with a resistance
of 120
Ω
The first and the
last system must
be terminated
with a resistance
of 120
Ω
.
(control computer)
ALTERNATIVE:
a solid
soldered
connection
or