INSTALLER: 5. Installer settings
21
After the weighing bars have been connected to the ILM.1 , check the system for correct functioning.
Control the value at Read out (function key System --> 2. Weigher data ). This is usually a value
between -400000 and -300000, of which the last numbers are changing continuously. When loaded
this value approaches 0 (will become less negative).
If the Read out value remains 0, the weighing bars are incorrectly connected. If this value becomes
more negative when loaded, the +INP and -INP have been exchanged. In both cases check the
connections before continuing.
Calibration procedure
1) Determination of the zero
ENSURE THE WEIGHING HOPPER IS EMPTY!
•
Select Installation --> 2. Calibration weigher.
The following will appear on the display:
•
Press .
The cursor starts flashing at the end of the line.
•
Press .
NO changes into YES.
•
Press .
YES changes into NO.
5.2 INSTALLATION option 2 Calibration weigher
21
1x
1x
22
21
#
#
Setting to zero
Agreed? NO
Weight 0.00
Standard weight
0.00
Agreed? NO
Measured consumption
0