background image

Lumina 17

 

Installer 

 

 

 

29 

 

 

Pre-run time

 

Setting of the time in which the air inlets go to the required position, before the fans 
activate. 

During Nat.Vent

 

Setting indicating if the extra inlets are open or closed during natural ventilation. 

 

CLOSED

: close (normal setting) 

 

FOLLOW INLET

: if the extra inlet has to 'follow' the normal air inlet (for example for 

extra curtains that must also open with natural ventilation). 

 

INSTALLER

 

 

VENTILATION

 

 

INLETS

 

 tab page 

Natural

 

 

 

Combi start/stop 

 

Position low

 

Setting of transitional position when a switch is made from very low mechanical ventilation 
to natural ventilation. The corresponding temperature is shown between brackets (based 
on the actual settings). 

Combi start/stop 

 

Position high

 

Setting of the transitional position when a switch is made from natural ventilation to strong 
mechanical ventilation. The corresponding temperature is shown between brackets 
(based on the actual settings). 

Damping

 

Setting of the opening/closing speed of air inlets during natural ventilation.   

Min. Waittime

 

Setting of the minimum wait time for transition. Within this time the controller cannot go 
back to natural ventilation. 

6.2

 

Heating, cooling and humidification 

6.2.1

 

Settings heating controls 

 

INSTALLER

 

 

HEAT COOL HUM

 

 tab page 

Heat

 

 

 

Description

 

Setting of the name of the function. 

Temp. Inputs

 

Setting the addresses of the analog inputs. If the temperature sensors have not been 
assigned, the control computer will use the house temperature. 

Содержание LUMINA 17

Страница 1: ...LUMINA 17 LUMINA 17 LUMINA 17 TOUCH F17 INSTALLATION MANUAL VERSION A2 g...

Страница 2: ...d by Fancom For the latest information about product installation and operation please contact the customer service dept and or the technical service dept of the Fancom company concerned In spite of t...

Страница 3: ...18 4 4 Communication 18 4 5 IO Test 19 5 House setup 20 5 1 House set up 20 6 Installer 23 6 1 Ventilation 23 6 2 Heating cooling and humidification 29 6 3 Clocks 32 6 4 Registration 33 6 5 Outside c...

Страница 4: ...e manual This manual also applies to other control computers in the Fancom F2000 line Always read the safety instructions and warnings carefully before using the control computer Always keep this manu...

Страница 5: ...ce Center 1 4 F Central FarmManager Virtually all Fancom equipment can be controlled and managed from a central location This requires the F Central FarmManager software package and a communication mo...

Страница 6: ...ependent on the outside conditions than with natural ventilation Several more fans are generally used with mechanical ventilation The fans used with specific ventilation percentages are indicated in t...

Страница 7: ...0 100 A 0 0 0 0 0 16000 40 0 0 M6 55 100 A 1 0 0 0 0 22000 55 0 0 M7 66 100 A 1 1 0 0 0 26400 66 0 0 M8 75 100 A 1 1 1 0 0 30000 75 0 0 M9 88 100 A 1 1 1 1 0 35200 88 0 0 M10 100 100 A 1 1 1 1 1 40000...

Страница 8: ...required ventilation level is 28 This percentage is between positions M3 and M4 The control computer uses the following settings Controllable fans and the extra controllable fans 62 activated Contr E...

Страница 9: ...ons M3 and M4 The control computer uses the following fans Both fans are controlled on for 75 of the set cycle time midway between M3 and M4 If the ventilation level increases further so will the modu...

Страница 10: ...switched off To prevent toggling the system must have been out of the natural phase for a certain time before system returns to the natural phase again Transition natural ventilation low ventilation...

Страница 11: ...n times Modulating control with optimized modulation times Rotating modulation These types are explained in the next sections This explanation is also important with linear controlled fans Linear cont...

Страница 12: ...is longer than the maximum cycle time of 10 minutes The control computer will calculate new ON and OFF times based on the maximum cycle time as follows 1 10 of 10 minutes means an ON time of 1 minute...

Страница 13: ...explained below 2 2 1 Relay ON OFF control The control computer activates heating if the house temperature drops below Setpoint hysteresis If the house temperature rises the heating will stay on until...

Страница 14: ...puter can be used to control a cooling unit Enter to which analog inputs the temperature sensor s have been connected and to which relay the cooling has been assigned Also enter the type of relay cont...

Страница 15: ...y control ON OFF or MODULATING See also Settings humidity page 31 The control computer has two types of humidity control 1 ON OFF control Humidifying activates as soon as humidity in the house drops b...

Страница 16: ...house temperature is lower than setpoint house temperature This means the heating will activate earlier and the difference between the actual and required house temperature will be smaller The control...

Страница 17: ...limate settings Settings of ventilation heating cooling and humidification 4 Clocks registration and external alarms Settings of the clocks input for external registration and outside climate 5 Extern...

Страница 18: ...24 hour time indication Time and Date Setting of the current time and date Computer name Setting of the name of the control computer Computer number Setting of the sequence number of the control comp...

Страница 19: ...n When the correct password has been entered all user screens can be accessed The system will request the password again if the controller is not used for a few minutes Change password EditMode Settin...

Страница 20: ...he control computer type FBU Data saved on one control computer can only be loaded into another control computer if both computers are of the same type In addition the set control computer numbers mus...

Страница 21: ...rol computer e g AI 4 SYSTEM COMMUNICATION tab page I2C Reset counters Setting used to reset all data to zero simultaneously The I O net is a connection for intelligent network modules For example Int...

Страница 22: ...l diagnostic data It is intended to be used as a service tool to find communication errors SYSTEM COMMUNICATION tab page Slaves Reset counters Setting used to reset all data to zero simultaneously 4 5...

Страница 23: ...ement is used If RH measurement is used the RH influence on heating cooling and ventilation can be used Humidification Setting indicating if humidity control is used This can only be used in combinati...

Страница 24: ...ing indicating if vortex damper control is used A vortex damper is always controlled analog There is one vortex damper control per extra switched fan Natural ventilation Setting indicating if natural...

Страница 25: ...ased on the curve Data linked to animals Setting indicating that clocks are only to be controlled if there are animals in the house Ventilation standard Setting used to determine how the minimum venti...

Страница 26: ...able must be fully entered Even if natural ventilation is used the relays at these position must be assigned This prevents ventilation being completely switched off if the user temporarily switches of...

Страница 27: ...or the modulating fans Relay 0 fan off 1 fan on M modulating fan This option is only possible if modulating fans are used INSTALLER VENTILATION COMBI tab page Inlet Position Readout of the ventilation...

Страница 28: ...on If it takes too long before the control computer proceeds to another position select FAST Centr vent Setting for using central inlet or central exhaust INSTALLER VENTILATION SETTINGS tab page Cont...

Страница 29: ...ng fans Modulating OPTIMAL Modulate under Setting of the ventilation percentage below which the control computer will apply modulating control to the linearly controlled part Optimal ON time Setting o...

Страница 30: ...s of the control part INSTALLER VENTILATION SETTINGS tab page Relay Rotation time Setting of the period after which the relays rotate Combi relays Setting of the number of the relays in the combi tabl...

Страница 31: ...the house If the wind comes from this direction positions under wind side the ventilation control may be influenced Modulate link Setting indicating if these air inlets are to be included in modulatin...

Страница 32: ...ure is shown between brackets based on the actual settings Combi start stop Position high Setting of the transitional position when a switch is made from natural ventilation to strong mechanical venti...

Страница 33: ...r only applies the OptiSec correction if the actual house temperature has fallen below the setpoint house temperature during the wait time For example set a wait time of 2 hours The control computer w...

Страница 34: ...etting for the analogue output address choice LINEAR or relay output choice RELAY Relay type Setting of the type of relay control ON OFF or MODULATING Evaporative cooling Setting indicating if evapora...

Страница 35: ...y output choice RELAY Relay type Setting of the passive not controlled relay status N O normally open if it makes no contact N C normally closed if it makes contact 6 3 2 Feedclock INSTALLER CLOCKS TI...

Страница 36: ...imum frequency of 20 pulses per second 20 Hz only use when there is a link with a switch clock CONTACT As long as the sensor makes contact the value will be added up cumulatively The amount is therefo...

Страница 37: ...if INT is selected Address Setting the address of the analog input Measurement outside RH Setting if the control computer carries out outside measurement concerned itself INT or via the communication...

Страница 38: ...nside climate INSTALLER INSIDE CLIMATE Temp inputs Setting for the addresses of the temperature inputs Pressure Input Setting the address of the analog input Speed press contr Setting of the speed at...

Страница 39: ...Setting of the passive not controlled input status N O CONTACT normally open if it makes no contact N C CONTACT normally closed if it makes contact iPRODUCTS to receive alarms from an intelligent mod...

Страница 40: ...5 C within 2 minutes The control computer monitors to that effect the current house temperature every 30 seconds and compares it with the values of the last 2 minutes 8 1 Operation In addition to the...

Страница 41: ...the passive not controlled relay status N O normally open if it makes no contact N C normally closed if it makes contact Alarm type Setting for the way in which the alarm will be processed LOUD Loud...

Страница 42: ...t or output 9 1 Addresses The address of the chosen connection must be entered at various places in the system settings An input or output address consists of two parts separated by a decimal point NN...

Страница 43: ...inputs have the following settings Input address The address of the analog input Type Setting of the type of measurement being carried out NONE LEVEL COUNT FREQ DSR feedback 9 5 Analog outputs Analog...

Страница 44: ...l voltage of the analog output 9 6 Digital outputs Digital outputs have the following settings Output address The address of the output Type of channel Shows the type of relay being used NONE ON OFF M...

Страница 45: ...Open contact voltage 12Vdc Low level 1 0Vdc Application Counter input min pulse width 25mSec max frequency 20Hz Application Frequency input max frequency 5kHz 5 Digital outputs Relays Relays 1 2 3 ma...

Страница 46: ...Lumina 17 Technical specifications 43 10 1 Interior control computer 1 Touch screen 2 HI mainboard 3 SBC 4 LED strip 5 FUNC CPU 6 IOB 4 I O 7 FDP25 Power supply 8 FRM 8 Internal relay 10 2 FDP25...

Страница 47: ...fications 44 10 3 IOB 4 AI type Type analog input Voltage measurement U Resistance measurement R AO 4 Analog outputs AI 4 Analog inputs DI 4 Digital inputs Relay 4 Digital outputs relays DO 8 Extra di...

Страница 48: ...terminal resistor Example Setting the I O net terminal resistor 1 One control computer connected to two I 0 network modules using one I O net The control computer is located between the two I O netwo...

Страница 49: ...s Industrieterrein 34 Place Panningen the Netherlands Hereby declares that Lumina 17 Satisfies the conditions of 1 The Low Voltage Directive 2006 95 EC according to EN 61010 2 the EMC Guideline direct...

Отзывы: