Lumina 17
System
19
FNet is the Fancom Network. Several control computers can be linked via this network. FNet is also used to operate
the connected control computers from a connected PC.
SYSTEM
COMMUNICATION
tab page
FNet
Reset counters
Setting used to reset all data to zero simultaneously.
If there is no S2S communication, the Receive and Transmit counters should be set to 0.
Tab page Slaves shows the connected I2C modules and IO-Net modules and additional diagnostic data. It is
intended to be used as a service tool to find communication errors.
SYSTEM
COMMUNICATION
tab page
Slaves
Reset counters
Setting used to reset all data to zero simultaneously.
4.5
IO-Test
Use the Input (I) and Output (O) test menu to set the control computer to test the communication channels.
In the IO-test menu inputs can be readout and outputs controlled at system level
SYSTEM
IO-TEST
The functions in the IO-test menu stop all the control actions of the control computer. Only use this to
quickly test IO functions.
This function may only be used by qualified personnel, as parts of the installation may be damaged with
direct control.