Lumina 17
Installer
23
6.
Installer
This chapter explains all the options in the
INSTALLER
menu.
6.1
Ventilation
6.1.1
Ventilation – Combi-table
In the combi-table the relationship between ventilation and air inlets for the entire ventilation path is entered. For
more information about the combi-table, see “Combi-table page 4.
All the positions in the combi-table must be fully entered. Even if natural ventilation is used, the relays at
these position must be assigned. This prevents ventilation being completely switched off if the user
(temporarily) switches off natural ventilation.
INSTALLER
VENTILATION
COMBI
tab page Exhaust
Enter the following per position:
Position %
Setting of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
The combi positions are also used for natural ventilation.