Lumina 17
Installer
24
Con. % /
Con. Extra / Relay 0-1
Your entry depends on a system setting set by the installer:
•
LINEAR
(
Con. %
)
Enter the positions of the linear controllable fans.
•
Con. Extra
(This column is only active if extra fans are used in the controllable part)
Control of extra fan
Settings: Position 0-R for relay
Setting: Position 0-A for linear
•
RELAY
(
Mod. %
)
(This column is only present if modulating fans are used)
The control computer uses the set ventilation percentage to calculate the on and off
times for the modulating fans.
Relay
0 = fan off
1 = fan on
M = modulating fan (This option is only possible if modulating fans are used)
INSTALLER
VENTILATION
COMBI
tab page
Inlet
Position %
Readout of the ventilation percentage at which fans should activate/deactivate and air
inlets open/close. The ventilation percentages must increase from the lowest to the
highest position.
Inlet %
Setting of the required inlet positions.
Extra %
Setting of the required extra inlet positions.
Pressure Pa
Setting of the required pressure for the corresponding position. A rule of thumb: the
higher the ventilation position, the lower the required pressure. Enter 0 to deactivate
pressure control.
INSTALLER
VENTILATION
COMBI
tab page
Cap.