Synergy Series Soft Start User Manual
MAN-SGY-017. Version 01. 27/06/2016
28
24Vdc Specification
24Vdc 60W
Residual ripple 100mV
Spikes/switching Peaks 240mV
Turn On/Off response
No overshoot of V out
Overvoltage voltage protection output
voltage must be clamped to <30Vdc
2.8 Electrical Connections
Model No (s):
US (+10% -15%
)
UC (+10% -15%)
Notes
SGY-101-4-01 to SGY-305-4-01
110 - 230Vac or 24Vdc
110Vac or 230Vac or
24Vdc.230Vac factory
default. 230Vac défaut
d’usine.#4
The system can have either a 110/230Vacmains
or 24Vdc input NOT both.
Le système peut avoir soit une alimentation principale
de 110/230 Vac ou de 24 Vdc, mais en aucun cas les
deux simultanement.
SGY-307-4-02 / SGY-309-4-02
110Vac
SGY-307-4-03 / SGY-309-4-03
230Vac
SGY-401-4-02 to SGY-503-4-02
110V ac
SGY-401-4-03 to SGY-503-4-03
230Vac
Notes
#1
The programmed digital input setting on D1COM,
D1-1I
,
D1-2I
mus
t correspond to the voltage applied to these terminals to avoid risk of damage to the equipment. Afin d’éviter
d’endommager l’équipement, le réglage de l’entrée numérique programmé sur D
1
COM, D
1
-
1I
, D
1
-2
I
doit correspondre à la tension appliquée à ces bornes.
#2
The programmed digital input setting on D2COM, D2-1I mus
t correspond to the voltage applied to these terminals to avoid risk of damage to the equipment. Afin d’éviter
d’endommager l’équipement, le réglage de l’entrée numérique programmé sur D2COM,
D2-1I
doit correspondre à la tension appliquée à ces bornes.
#3
The control supply can be 110 to 230Vac applied to the N, L terminals or 24Vdc applied to the 0Vdc, 24V input terminals. The correct voltage as specified must only be applied to
one of these supply inputs to avoid risk of damage to the equipment.
L’alimentation contrôle peut être 110 ā 230 Vca, appliquée aux bornes N et L, ou
24 Vcc, appliquée aux bornes d’entrée de 0 Vcc, 24 V. Afin d’éviter d’endommager l’équipement,
la tension appropriée selon les indications ne doit être appliquée qu’à une entrée d’alimentation.
#4
See Section 3.10
Référer au la Manuel de Programmation Synergy MAN-SGY-
001 pour des paramètres par défaut d’usine
Required rating
Programmable
Default
Description
Representative of terminal label. See TABLE 1, U
S
for AC supply
rating as marked on actual Synergy model
Description
Default
Programm-able
Required rating
#1
Group 1 input
common
group 1 relay
common
#1
SEE TABLE 1, UC
yes
start/
stop
opto-coupled
input
relay N/C
fault
yes
230Vac 1A AC15,
30Vdc 0.5A Resistive
#1
SEE TABLE 1, UC
yes
None
opto-coupled
input
relay N/O
fault
yes
230Vac 1A AC15,
30Vdc 0.5A Resistive
group 2 input
common
group 2 relay
common
SEE TABLE 1 ,UC
yes
reset
opto-coupled
input
relay N/O
running
yes
230Vac 1A AC15,
30Vdc 0.5A Resistive
not used
relay N/O
end of start
yes
230Vac 1A AC15,
30Vdc 0.5A Resistive
3 x PTC in series
(130°C)
OFF
thermistor
analog
output
0-10V
yes
0 to 10V 10mA /
4-20mA
3 x PTC in series
(130°C)
OFF
thermistor
analog 0V
0V
signal ground
analog input
0-10V
Yes
0 to 10V 10mA /
4-20mA
#3
SEE TABLE 1 US
control supply
control
supply
SEE TABLE 1 , US
#3
#3
SEE TABLE 1 US
control supply
control
supply
SEE TABLE 1, US
#3
2. Electrical Installation (continued)
Содержание synergy
Страница 1: ...Innovation in soft start technology synergytm USER MANUAL MAN SGY 017 Version 01...
Страница 20: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 20 Blank Page...
Страница 27: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 27 Blank Page...
Страница 33: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 33 Blank Page...
Страница 84: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 84 Blank Page...
Страница 100: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 100 Blank Page...
Страница 106: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 106 Blank Page...
Страница 112: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 112 Blank Page...
Страница 129: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 129 Blank Page...
Страница 197: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 197 Blank Page...
Страница 204: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 204 Blank Page...
Страница 231: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 231 Notes...
Страница 232: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 232 Notes...
Страница 233: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 233...