Synergy Series Soft Start User Manual
MAN-SGY-017. Version 01. 27/06/2016
147
Address
Description
Min/Max
Units
Read/
Write
Address:33536 ( 8300 hex )
Format: 32 bit unsigned
Note: Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
I1
The RMS current on phase L1
0
0
0 ( 0 hex ) 0
10000000 ( 989680 hex )
10000
0 ( 0 hex ) 0
A
R
Address:33538 ( 8302 hex )
Format: 32 bit unsigned
Note: Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
I2
The RMS current on phase L2
0
0
0 ( 0 hex ) 0
10000000 ( 989680 hex )
10000
0 ( 0 hex ) 0
A
R
Address:33540 ( 8304 hex )
Format: 32 bit unsigned
Note: Linear Scaling (1 = 1mA)
Current (A) = (Value / 1000)
I3
The RMS current on phase L3
0
0
0 ( 0 hex ) 0
10000000 ( 989680 hex )
10000
0 ( 0 hex ) 0
A
R
Address:34688 ( 8780 hex )
Format: 32 bit unsigned
Note: Linear Scaling (1 = 1W)
True Power (KW) = (Value / 1000)
True Power P
Total true power
This is an addition of the 3 phases
0
0 ( 0 hex ) 0
10000000 ( 989680 hex )
10000
0 ( 0 hex ) 0
kW
R
Address:34816 ( 8800 hex )
Format: 32 bit unsigned
Note: Linear Scaling (1 = 1VA)
Apparent Power (kVA) =
(Value/1000)
Apparent Power S
Total Apparent Power
This is an addition of the 3 phases
0
0 ( 0 hex ) 0
10000000 ( 989680 hex )
10000
0 ( 0 hex ) 0
kVA
R
Address:34944 ( 8880 hex )
Format: 32 bit unsigned
Note: Linear Scaling (1 = 1Var)
Reactive Power (kVar) = (Value /
1000)
Reactive Power Q
Total Reactive power
This is an addition of the 3 phases
0
0 ( 0 hex ) 0
10000000 ( 989680 hex )
10000
0 ( 0 hex ) 0
kvar
R
Address:35008 ( 88C0 hex )
Format: 16 bit unsigned
Note: Linear Scaling ( 1 =
0.006104 % )
iERS Saving Level
Indicates the level of potential
saving
100% indicates that Unit is saving
at its maximum level
0
0 ( 0 hex ) 0
16384 ( 4000 hex ) 100
0 ( 0 hex ) 0
%
R
Address:35200 ( 8980 hex )
Format: 16 bit unsigned
Note: Linear Scaling ( 1 = 1 V )
Fixed Voltage
User settable voltage level for
power calculations
If required can be used to improve
accuracy of power calculations
0
100 ( 64 hex ) 100
500 ( 1F4 hex ) 500
500 ( 1F4 hex ) 100
V
R/W
Address:35264 ( 89C0 hex )
Format: 8 bit unsigned
Note: Binary value
Fixed Voltage
Selects the source for the voltage
value used in the power
calculations.
on: KW KVar and KVA are
calculated using the "Fixed
Voltage"
off: KW KVar and KVA are
calculated using the internally
measured voltage.
0 ( 0 hex ) Off
1 ( 1 hex ) On
0 ( 0 hex ) Off
R/W
5. Modbus RTU Parameter Table (continued)
Содержание synergy
Страница 1: ...Innovation in soft start technology synergytm USER MANUAL MAN SGY 017 Version 01...
Страница 20: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 20 Blank Page...
Страница 27: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 27 Blank Page...
Страница 33: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 33 Blank Page...
Страница 84: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 84 Blank Page...
Страница 100: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 100 Blank Page...
Страница 106: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 106 Blank Page...
Страница 112: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 112 Blank Page...
Страница 129: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 129 Blank Page...
Страница 197: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 197 Blank Page...
Страница 204: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 204 Blank Page...
Страница 231: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 231 Notes...
Страница 232: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 232 Notes...
Страница 233: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 233...