Synergy Series Soft Start User Manual
MAN-SGY-017. Version 01. 27/06/2016
161
Address
Description
Min/Max
Units
Read/
Write
Address:53807 ( D22F hex )
Format: 8 bit unsigned
Note: Binary value
L1-L3-L2 Trip
Determines if supply phase
sequence is incorrect for motor
rotation
On : Trips if the phase sequence is
L1-L3-L2.
Off : The Unit will continue to
operate normally
0 ( 0 hex ) Off
1 ( 1 hex ) On
0 ( 0 hex ) Off
R/W
Address:53808 ( D230 hex )
Format: 8 bit unsigned
Note: Binary value
L1-L2-L3 Trip
Determines if supply phase
sequence is incorrect for motor
rotation
On : Trips if the phase sequence is
L1-L2-L3.
Off : The Unit will continue to
operate normally
0 ( 0 hex ) Off
1 ( 1 hex ) On
0 ( 0 hex ) Off
R/W
Address:59392 ( E800 hex )
Format: 16 bit unsigned
Note: 0 = Local, 1 = User, 2 =
TwoWire,
3 = ThreeWire, 4 = Modbus
Control Method
Local Touch Screen : Control using
the button on the keypad
User Programmable : Control
using the terminals. Function
defined in "I/O" menu
Two Wire Control : Control using
terminals. Functions fixed as
shown on screen
Three Wire Control : Control using
terminals. Functions fixed as
shown on screen
Modbus Network : Control via
remote Modbus network or
remote Keypad or Modbus TCP
0 ( 0 hex ) Local Touch Screen
4 ( 4 hex ) Modbus Network
0 ( 0 hex ) Local Touch Screen
R/W
Address:60608 ( ECC0 hex )
Format: 16 bit unsigned
Note: Linear Scaling ( 1 =1 )
See Trip Code Descriptions
Last Trip
Displays the last Fault trip
0
0
0 ( 0 hex ) 0
65535 ( FFFF hex ) 65535
0 ( 0 hex ) 0
R
Address:60609 ( ECC1 hex )
Format: 16 bit unsigned
Note: Linear Scaling ( 1 =1 )
See Trip Code Descriptions
Last Trip -1
Displays the last Fault trip -1
0
0
0 ( 0 hex ) 0
65535 ( FFFF hex ) 65535
0 ( 0 hex ) 0
R
Address:60610 ( ECC2 hex )
Format: 16 bit unsigned
Note: Linear Scaling ( 1 =1 )
See Trip Code Descriptions
Last Trip -2
Displays the last Fault trip -2
0
0
0 ( 0 hex ) 0
65535 ( FFFF hex ) 65535
0 ( 0 hex ) 0
R
Address:60611 ( ECC3 hex )
Format: 16 bit unsigned
Note: Linear Scaling ( 1 =1 )
See Trip Code Descriptions
Last Trip -3
Displays the last Fault trip -3
0
0
0 ( 0 hex ) 0
65535 ( FFFF hex ) 65535
0 ( 0 hex ) 0
R
5. Modbus RTU Parameter Table (continued)
Содержание synergy
Страница 1: ...Innovation in soft start technology synergytm USER MANUAL MAN SGY 017 Version 01...
Страница 20: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 20 Blank Page...
Страница 27: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 25 07 2016 27 Blank Page...
Страница 33: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 33 Blank Page...
Страница 84: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 84 Blank Page...
Страница 100: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 100 Blank Page...
Страница 106: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 106 Blank Page...
Страница 112: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 112 Blank Page...
Страница 129: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 129 Blank Page...
Страница 197: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 197 Blank Page...
Страница 204: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 204 Blank Page...
Страница 231: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 231 Notes...
Страница 232: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 232 Notes...
Страница 233: ...Synergy Series Soft Start User Manual MAN SGY 017 Version 01 27 06 2016 233...