Accessory
Electrical connections
Dip-switches and LED indication of their functions
English
28
4
DIP-SWITCH 4 and 8
ON
: pre-flashing before opening
OFF
: without pre-flashing
8
ON
: flasher desactivated during pause in
automatic operation (with
dip 3 = ON
)
OFF
: it flashes during pause in automatic
operation (with
dip 3 = ON
)
ELPRO 64
JUNIOR 624
ELECTRICAL CONNECTIONS TO THE TERMINALS AND THEIR FUNCTIONS
Photocells in closing
Warning lamp output
24 V - 1 W
24 Vdc output
Flashing lamp
24 Vdc
ZERO.PH
Orbita 57
8
9
13
1 14
4
10
9
Output for a possible automation status
warning lamp:
Warning lamp
on
= gate open
Warning lamp
off
= gate closed
Flashing at
0,5 s (fast)
= closing movement
Flashing at
1 s (normally)
= opening
movement
24 Vdc OUTPUT for max load:
n° 2 pairs of photocells
n° 1 radio receiver
n° 1 led key-switch Chis 37 / Chis-E 37
All the instructions are attached to their
respective command accessories
OUTPUT 24 Vdc for flashing lamp
NC
NC
1 2
All of the
NC contacts
on the
photocells in
closing phase
must be
connected in series to the terminals 1
and 2
1
DIP-SWITCH 1
ON
: stops gate on opening and reverses it on
closing once obstacle is removed
OFF
: no stop on opening, gate is reversed on
closing in case of an obstacle
L2 green on
: no obstacle, it turns off in case of
obstacle
Key-switch
CO
MM
ON
O
PEN
C
L
OS
E
S
T
O
P
NC
3 4 5 6
NO and NC contacts to be connected
to the respective terminals of the key or
button-switches.
All the possible configurations are
attached to their respective command
accessories
L4 red off
: no contact OPEN, it lights up with
each opening impulse
L5 red off
: no contact CLOSE, it lights up with
each closing impulse
L6 green on
: STOP contact closed, it turns off at
each stop contact
Radio contact
COMMO
N
RADIO
CONTACT
2
5
3
7
By connecting any NO contact
between the two terminals, each
impulse can perform:
- Only opening:
dip 2 = ON
and
dip 5 = OFF
- Reverse direction on each impulse
dip 2 = OFF
and
dip 5 = OFF
- Step by step: open-stop-close-stop
dip 2 = OFF
and
dip 5 = ON
DIP-SWITCH 2 and 5
(MUST NOT ever be simultaneously ON):
ON
: does not reverse and does not stop in
opening
OFF
: in opening always stops and reverses
ON
: step by step with intermediate stop
OFF
: reverses direction on every impulse
L7 red off
: no RADIO contact, it lights on at
every impulse to radio contact
Output 24 Vdc
for DSA control
10
24 Vdc output to power the photocell
trasmitters (connected in parallel) for the
DSA
control:
A
utotest
S
afety
D
evice = if
activated, before opening or closing
movements all the security devices are
checked for faults.
In case any malfunction is detected, the
operator is prevented from starting and the
LED on the Junior cover keeps flashing with
alternated blue and orange lights.
DIP-SWITCH 10
ON
: DSA control of the photocells.
The photocell projectors, outputs 13-14, must
be powered
OFF
: No DSA control of the photocells
VIX 53
ZERO.K
ZERO.EK