6.4 SETUP
The SET-UP procedure consists of a series of move-
ments during which the board acquires the length
of travel and other leaf parameters. The SETUP
procedure also registers the BUS 2easy devices that
are present.
SETUP needs to be carried out:
-
when
S0
flashes on the display (e.g. when the
automation is first put into operation)
-
after a board has been replaced
-
if you wish to modify the length of travel of the
leaves
-
if there are active errors that require the SETUP
procedure to be carried out
-
if programming functions are modified that require
a new SETUP
Checks prior to SETUP:
-
the automation must not be set to manual mode
-
the STOP input, if not used, must be bridged
-
make sure that the settings of the following func-
tions in Basic Programming are correct:
cF
type of automation
Mn
number of motors
En
encoder (has to be enabled, if present)
!
While the SETUP procedure is being carried out,
prevent transit in the area of movement of the leaves
because the safety devices are disabled.
1. Go to the
tl
function in basic programming. The
value displayed is
--
.
The leaves must be closed. To close them now,
press the
++
button for Leaf1 and the
--
button
for Leaf2.
2. Press the
++
and
--
buttons simultaneously for a
few seconds.
The display flashes, then the first movement starts
and
S1
appears on the display.
Release the buttons.
3. SETUP starts. The display indicates the current phases
with a flashing code (from
S1
to
S4
, see
SETUP
phases).
If the SETUP procedure doesn’t start or stops before it
has been completed, the board exits from program-
ming mode and
S0
flashes on the display: check the
ERRORS that are present (Chapter § Diagnostics).
4
SETUP phases
Display Phase
S1
Leaf1 opens:
searching for the OPEN position
S2
*
Leaf2 opens:
searching for the OPEN position
S3
*
Leaf2 closes:
searching for the CLOSED position
S4
Leaf1 closes:
searching for the CLOSED position
00
SETUP has been completed. The board exits from
programming mode and the display shows the automa-
tion status - closed.
* phase NOT carried out in the case of a single leaf automation.
The phases are carried out automatically in sequence.
The open/closed position is recognised according to
the system configuration:
■
Timed operation
An OPEN A command is sent as soon as the leaf reaches
the mechanical stop.
■
Operation with encoder
The board automatically recognises the position if a
mechanical stop is present.
If there is no mechanical stop, an OPEN A command
is sent at the point in which you want the leaf to stop.
■
Operation with limit switches (with or without encoder)
If the limit switch is programmed to specify the stop-
ping point, the board automatically recognises the
position as soon as the limit switch is triggered.
If the limit switch is programmed to specify the slow-
down point, it sends an OPEN A command as soon as
the leaf reaches the mechanical stop.
■
Sliding gate
The board automatically recognizes the positions
when each limit switch is triggered.
In this application, the limit switch is used only as a
stop device.
!
The limit switches in this application are indispen-
sable.