23

 

Note

: The behavior of the warning light varies 

according to the logic you have set: 

Logics A, S, E, EP, and B

: The warning light 

is on steadily during opening and the pause 
phase. During closing, the light flashes. 
 

Logic C

: The warning light is on steadily 

during opening and flashes during closing. 

Set Other Operating Controls 

WARNING

! Turn off the main power before 

you make any electrical connections or set any 
switches inside the control panel box. 

Note

: Some DIP switch assemblies are labeled 

differently depending on their date of 
manufacture. OPEN indicates 

off

 and ON 

indicates 

on

You need to set DIP switches and adjust some 
potentiometers on the control panel for your gate's 
operation. The 450 MPS Control Panel has 5 DIP 
switches and 4 potentiometers that control a wide range 
of functions. 
 

Set DIP Switches 

Switches 1, 2, and 3 (Operating Logic)

: The 450 MPS 

Control Panel offers six operating modes:  

• 

A (automatic) 

• 

S (security) 

• 

E (semi-automatic) 

• 

EP (semi-automatic, step by step) 

• 

B (manned, pulsed) 

• 

C (manned and constant) 

Refer to the operating logic tables later in these 
instructions for more detail. 
 
Switches 1, 2, and 3 control the operating logic 
according to the following scheme:  

 

DIP Switch 

Logic 

1 2 3 

A  off off off 

S on off off 

E  off on off 

EP on on off 

B  on on on 
C off off on 

 
 

Switch 4 (Reversing Device Behavior on Closing)

Refer to the operating logic tables later in these 
instructions and to the chart below for how to set DIP 
switch 4. 
 

Gate Behavior 

During Closing 

DIP Switch 4 

Gate immediately 
reverses its direction 

off 

Gate stops and reverse its 
direction when reversing 
device is no longer 
triggered 

on 

 
 

Switch 5 (Reversing Stroke)

: Some electric locks 

require a reversing stroke to disengage the lock. If your 
lock requires this reversing stroke, set DIP switch 5 
according to the following chart. 
 

Reversing Stroke 

DIP Switch 5 

Not activated 

off 

Activated on 
 

 

Adjust the Potentiometers 

The four potentiometers control the torque (or 
pressure), the pause time between opening and closing, 
the opening/closing time of operation, and the leaf delay 
on closing.

 

 
Torque (Pressure)

:

 The torque (or pressure) 

potentiometer on the 450 MPS must be turned all the 
way clockwise for the 750 Operator. The potentiometer 
controls voltage to the operator, which can affect the 
life of the operator’s motor. The torque/pressure 
potentiometer cannot be used to adjust the operator’s 
hydraulic operating pressures.  

Caution

: Failure to turn the torque/pressure 

potentiometer to maximum in the clockwise 
direction jeopardizes the life of the motor of 
your operator.  

WARNING

! Adjust the operating pressure on 

the 750 Operator only by means of the 
hydraulic bypass valve screws. See pages 18 
and 24. 

Содержание 750 Standard

Страница 1: ...the Drive Unit 12 Connect the Hydraulic Lines 12 Synchronize the Hydraulic System 13 Install the Gate Leaf Shoe 13 Install the Gate Leaf 15 Installing the Control Panel 15 Connect the Main Power Supp...

Страница 2: ...ortant that you locate the gate far enough away from the road to eliminate the potential of traffic getting backed up This distance is affected by the size of the gate how often it is used and how fas...

Страница 3: ...ipment observe some fundamental rules Do not touch the equipment with damp or humid hands or feet Do not install or operate the equipment with bare feet Do not allow small children or incapable person...

Страница 4: ...cluding shaft length width in cm 47 8 153 4 77 8 12 4 40 20 Weight 100 deg swing lb kg 180 deg swing lb kg 18 8 20 9 Oil quantity qt l 0 9 1 Maximum angle of rotation 100 deg swing deg 180 deg swing d...

Страница 5: ...ts base plate with 4 leveling bolts installed and with the sleeve fitted over the splined shaft 2 Box halves right angled and lipped pieces of galvanized steel that together form the sides of the box...

Страница 6: ...isengaged you can open and close the gate leaf by hand Such manual operation of the gate is necessary during installation and useful during power failures The two bypass valves are located on the fron...

Страница 7: ...them after pause time Opens single leaf connected to Motor 1 and closes it after pause time No effect No effect No effect Off Opening Closes both leaves immediately Closes the leaf immediately Stops S...

Страница 8: ...1 No effect opening is inhibited No effect opening is inhibited No effect opening is inhibited Off Opening Stops Stops Stops Stops gate closes when reversing device no longer triggered No effect On O...

Страница 9: ...50 Operator consists of the following steps Setting the concrete forms Installing the power unit Installing the drive unit Connecting the hydraulic lines Synchronizing the hydraulic system Installing...

Страница 10: ...x 18 in 25 4 x 45 7 cm Axis of rotation of gate leaf Gate post Minimum of 2 1 4 in 5 7 cm maximum of 5 1 4 in 13 3 cm One of 4 bolts that anchor plate into cement footing Figure 4 Recommended dimensio...

Страница 11: ...and then lift it off the box The vinyl hinges can now be placed in the hinge receptacles on the right hand side Secure the hinges with the screws provided You may surface mount the power unit box to...

Страница 12: ...e the necessary holes for the two hydraulic lines that run from the drive unit to the power unit Once you have made your access holes you can weld the box halves to the foundation plate and to one ano...

Страница 13: ...ruct a shear pin assembly to accommodate the extra vertical distance The assembly is welded to the bottom of the gate leaf shoe on one end and to the sleeve for the splined shaft of the pinion on the...

Страница 14: ...he bottom side of the U shaped section of the shoe as shown in Figure 10 On the bottom of the U shaped shoe section center the sleeve around the pilot hole that marks the axis or rotation Accurately c...

Страница 15: ...veling bolts on the base of the drive unit to correct any problems with the gate s travel Installing the Control Panel Locate the control panel in the most convenient position possible considering the...

Страница 16: ...anel box C 3 X 18 AWG 3 X 18 AWG 4 Main power switch D 5 X 18 AWG 5 X 18 AWG 5 Circuit breaker E 5 X 18 AWG 5 X 18 AWG 6 Main junction box F 4 X 14 AWG up 3 X 14 AWG up 7 Switch for 750 Operator to 41...

Страница 17: ...in block J1 and connect the power wires to the terminals labeled N neutral and L phase Caution The operators are grounded only by the grounded circuit the installer provides Connect One Activating Dev...

Страница 18: ...ystem has one operator connect the capacitor and the brown and black or red and black wires from your operator to the terminals 3 and 5 in block J2 for Motor 1 Connect the blue or white wire from the...

Страница 19: ...Panel U L Listed Control Panel Enclosure Cord grip or conduit from U L Listed gate operator s see text Ground Legend Red Black White Yellow Green a b J3 Figure 15 Wiring detail a inside the junction b...

Страница 20: ...the motor s direction of rotation replace any test circuits you installed between terminals 11 and 13 between 13 and 21 and between 14 and 15 with the proper reversing and stop devices The instructio...

Страница 21: ...J3 In addition terminal block J3 requires a fail safe connection for the photocells Connect the photocells to terminals 20 and 21 Activating Devices and Radio Receiver The acti vating devices and radi...

Страница 22: ...y when an activating signal is sent for 2 and 1 gate leaves respectively DL3 should be illuminated except when the stop button is pressed DL4 and DL5 should be illuminated except when the reversing de...

Страница 23: ...off EP on on off B on on on C off off on Switch 4 Reversing Device Behavior on Closing Refer to the operating logic tables later in these instructions and to the chart below for how to set DIP switch...

Страница 24: ...unit through the bleed screw holes see Fig ure 18 You need to bleed the hydraulic system before setting the gate up for normal operation To run the gate leaf through an open close cycle make sure the...

Страница 25: ...22 The location of the bleed screws on the drive unit top view WARNING The pressure the gate leaf applies to the obstruction is determined by the bypass valve adjustment It is the installer s respons...

Страница 26: ...the extension collar is affected by the overlap of the extension bar and extension U Attach the 750 extension collar to the bottom of the gate leaf with a 7 16 in 1 1 cm bolt Weld together the extens...

Страница 27: ...use check every 6 mo Check all reversing devices Every six months you should verify that all installed reversing devices work properly The Control Panel The control panel requires no maintenance Trou...

Страница 28: ...a reversing device is triggered If either does not illuminate then one of your reversing devices is preventing the gate from responding to your signal Check your reversing devices If no reversing dev...

Страница 29: ...use negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceedi...

Отзывы: