NC

COM

NO

LOCK

FSWTX W.LIGHT

30 Vcc

FSW

STOP

9      10     11   12   13    14   15    16   17    18   19   20   21    22   23    24   25

+

OP

CL

NC

B

A

+

+

4 Wire

Receiver

 

Figure 19. Connect a four-wire receiver 

 
 

Decoder Card

: If you are installing the Digicard 

magnetic card reader, or the Digikey keyboard, use the 
quick-fit connector J4 for the DS (formerly the MD01) 
decoder card (see Figure 13). 
 

Open/Hold Open Device

: To open and hold open the 

gate, an Open/Hold Open device must make a set of 
contacts across terminals 18 and 19 (or 16 and 17) and 
must break a set of contacts between terminals 13 and 
21 (see Figure 20).  
 

Stop Button

: The stop button you install must have 

normally closed (N.C.) contacts. Multiple stop buttons 
must be wired in series. Connect your stop device 
between terminals 14 and 15.  

Note

: If you choose not to install a stop button, 

you must install a circuit between these 
terminals for the control panel to work. 

The LED Indicators

: The five light-emitting diodes 

(LEDs) on the control panel can be used to check for 
the proper functioning of the devices you attach to the 
control panel. The LED lights are on whenever the 
contacts are closed across each of the respective 
terminals.  
 

LOCK

FSWTX W.LIGHT

30 Vcc

FSW

STOP

9      10     11   12   13    14   15    16   17    18   19   20   21    22   23    24   25

+

OP

CL

NC

B

A

+

+

Relay

24 VDC 

SPDT

Switch

NC

NO

COM

 

Figure 20. Connect an Open/Hold Open device 

with an external relay 

 

DL1 and DL2 should illuminate only when an 
activating signal is sent for 2 and 1 gate leaves, 
respectively. DL3 should be illuminated except when 
the stop button is pressed. DL4 and DL5 should be 
illuminated except when the reversing devices, for 
opening and closing, respectively, are triggered. Use the 
LEDs and the table below to determine if the accessory 
devices you have installed are operating properly.  
 

LED On  Off 

DL1,  
Open 2 leaves 

Command 
active 

Command 
inactive 

DL2,  
Open 1 leaf 

Command 
active 

Command 
inactive 

DL3, Stop 

Command not 
active 

Command 
active 

DL4,  
FTSW Open 

Opening 
reversing 
devices not 
triggered 

Reversing 
device triggered 

DL5,  
FTSW Close 

Closing 
reversing 
devices not 
triggered 

Reversing 
device triggered 

 
Electric Lock

: An electric lock can make use of the 

reversing stroke function controlled by DIP switch 5. A 
reversing stroke is a short closing phase that allows the 
electric lock time to disengage itself before the operator 
starts its opening. Use DIP switch 5 if necessary for 
your lock to function correctly. Connect your lock to the 
terminals 24 and 25. The terminals provide 12 VAC 
pulsed power. 
 
Connect a magnetic locking device as shown in Figure 
21, below. 
 

Warning Light

: Connect a warning light to terminals 

22 and 23 in the group labeled 

W.LIGHT

 in terminal 

block J3. The terminals provide an output voltage of 30 
VDC, maximum power 3 Watts. This output voltage 
will power most 24 VDC warning lights. 
 

Relay

24 VDC 

SPDT

Mag
Lock

+

NC

COM

LOCK

FSWTX W.LIGHT

30 Vcc

FSW

STOP

9      10     11   12   13    14   15    16   17    18   19   20   21    22   23    24   25

+

OP

CL

NC

B

A

+

+

 

Figure 21. Connect a mag lock to the 450 MPS 

control panel 

Содержание 750 Standard

Страница 1: ...the Drive Unit 12 Connect the Hydraulic Lines 12 Synchronize the Hydraulic System 13 Install the Gate Leaf Shoe 13 Install the Gate Leaf 15 Installing the Control Panel 15 Connect the Main Power Supp...

Страница 2: ...ortant that you locate the gate far enough away from the road to eliminate the potential of traffic getting backed up This distance is affected by the size of the gate how often it is used and how fas...

Страница 3: ...ipment observe some fundamental rules Do not touch the equipment with damp or humid hands or feet Do not install or operate the equipment with bare feet Do not allow small children or incapable person...

Страница 4: ...cluding shaft length width in cm 47 8 153 4 77 8 12 4 40 20 Weight 100 deg swing lb kg 180 deg swing lb kg 18 8 20 9 Oil quantity qt l 0 9 1 Maximum angle of rotation 100 deg swing deg 180 deg swing d...

Страница 5: ...ts base plate with 4 leveling bolts installed and with the sleeve fitted over the splined shaft 2 Box halves right angled and lipped pieces of galvanized steel that together form the sides of the box...

Страница 6: ...isengaged you can open and close the gate leaf by hand Such manual operation of the gate is necessary during installation and useful during power failures The two bypass valves are located on the fron...

Страница 7: ...them after pause time Opens single leaf connected to Motor 1 and closes it after pause time No effect No effect No effect Off Opening Closes both leaves immediately Closes the leaf immediately Stops S...

Страница 8: ...1 No effect opening is inhibited No effect opening is inhibited No effect opening is inhibited Off Opening Stops Stops Stops Stops gate closes when reversing device no longer triggered No effect On O...

Страница 9: ...50 Operator consists of the following steps Setting the concrete forms Installing the power unit Installing the drive unit Connecting the hydraulic lines Synchronizing the hydraulic system Installing...

Страница 10: ...x 18 in 25 4 x 45 7 cm Axis of rotation of gate leaf Gate post Minimum of 2 1 4 in 5 7 cm maximum of 5 1 4 in 13 3 cm One of 4 bolts that anchor plate into cement footing Figure 4 Recommended dimensio...

Страница 11: ...and then lift it off the box The vinyl hinges can now be placed in the hinge receptacles on the right hand side Secure the hinges with the screws provided You may surface mount the power unit box to...

Страница 12: ...e the necessary holes for the two hydraulic lines that run from the drive unit to the power unit Once you have made your access holes you can weld the box halves to the foundation plate and to one ano...

Страница 13: ...ruct a shear pin assembly to accommodate the extra vertical distance The assembly is welded to the bottom of the gate leaf shoe on one end and to the sleeve for the splined shaft of the pinion on the...

Страница 14: ...he bottom side of the U shaped section of the shoe as shown in Figure 10 On the bottom of the U shaped shoe section center the sleeve around the pilot hole that marks the axis or rotation Accurately c...

Страница 15: ...veling bolts on the base of the drive unit to correct any problems with the gate s travel Installing the Control Panel Locate the control panel in the most convenient position possible considering the...

Страница 16: ...anel box C 3 X 18 AWG 3 X 18 AWG 4 Main power switch D 5 X 18 AWG 5 X 18 AWG 5 Circuit breaker E 5 X 18 AWG 5 X 18 AWG 6 Main junction box F 4 X 14 AWG up 3 X 14 AWG up 7 Switch for 750 Operator to 41...

Страница 17: ...in block J1 and connect the power wires to the terminals labeled N neutral and L phase Caution The operators are grounded only by the grounded circuit the installer provides Connect One Activating Dev...

Страница 18: ...ystem has one operator connect the capacitor and the brown and black or red and black wires from your operator to the terminals 3 and 5 in block J2 for Motor 1 Connect the blue or white wire from the...

Страница 19: ...Panel U L Listed Control Panel Enclosure Cord grip or conduit from U L Listed gate operator s see text Ground Legend Red Black White Yellow Green a b J3 Figure 15 Wiring detail a inside the junction b...

Страница 20: ...the motor s direction of rotation replace any test circuits you installed between terminals 11 and 13 between 13 and 21 and between 14 and 15 with the proper reversing and stop devices The instructio...

Страница 21: ...J3 In addition terminal block J3 requires a fail safe connection for the photocells Connect the photocells to terminals 20 and 21 Activating Devices and Radio Receiver The acti vating devices and radi...

Страница 22: ...y when an activating signal is sent for 2 and 1 gate leaves respectively DL3 should be illuminated except when the stop button is pressed DL4 and DL5 should be illuminated except when the reversing de...

Страница 23: ...off EP on on off B on on on C off off on Switch 4 Reversing Device Behavior on Closing Refer to the operating logic tables later in these instructions and to the chart below for how to set DIP switch...

Страница 24: ...unit through the bleed screw holes see Fig ure 18 You need to bleed the hydraulic system before setting the gate up for normal operation To run the gate leaf through an open close cycle make sure the...

Страница 25: ...22 The location of the bleed screws on the drive unit top view WARNING The pressure the gate leaf applies to the obstruction is determined by the bypass valve adjustment It is the installer s respons...

Страница 26: ...the extension collar is affected by the overlap of the extension bar and extension U Attach the 750 extension collar to the bottom of the gate leaf with a 7 16 in 1 1 cm bolt Weld together the extens...

Страница 27: ...use check every 6 mo Check all reversing devices Every six months you should verify that all installed reversing devices work properly The Control Panel The control panel requires no maintenance Trou...

Страница 28: ...a reversing device is triggered If either does not illuminate then one of your reversing devices is preventing the gate from responding to your signal Check your reversing devices If no reversing dev...

Страница 29: ...use negligence or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceedi...

Отзывы: