Table 153: Power Specifications
Switch Model
X590-24t-1q-2c
X590-24x-1q-2c
AC Input: 100-127 VAC, 2.5 A max. per PSU, 50/60 Hz
AC Input: 200-240 VAC, 1.25 A max. per PSU, 50/60 Hz
DC Input: -48 to -60 VDC, 5.0 A max. per PSU
Table 154: Power and Heat Dissipation
Minimum
12
Heat
Dissipation (1 PSU)
Minimum
12
Power
Consumption
Maximum
12
Heat
Dissipation (2
PSUs)
Maximum
12
Power
Consumption
X590-24t-1q-2c-AC
310.97 BTU/hr
91.14 W
792.27 BTU/hr
232.20 W
X590-24t-1q-2c-DC
332.63 BTU/hr
97.49 W
833.62 BTU/hr
244.32 W
X590-24x-1q-2c-AC
278.42 BTU/hr
81.60 W
743.82 BTU/hr
218.00 W
X590-24x-1q-2c-DC
286.61 BTU/hr
84.00 W
786.12 BTU/hr
230.40 W
CPU, Memory
CPU/Memory
1GHz 64-bit CPU
2GB DDR3 ECC SDRA memory
4GB eMMC Flash Memory
12 MB buffer, per chip
Standards and Environmental Data
Table 155: Safety Standards
North American Safety of
ITE
UL 60950-1 2nd Ed., A2:2014, Listed Device (US)
CSA 22.2 #60950-1-07 2nd Ed., 2014-10 Canada)
Complies with FCC 21CFR 1040.10 (US Laser Safety)
CDRH Letter of Approval (US FDA Approval)
European Safety of ITE
EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013 2nd Ed.
EN 60825-1:2007 IEC 60825-1:2007 Class 1 (Lasers Safety)
2014/35/EU Low Voltage Directive
International Safety of ITE
CB Report & Certificate per IEC 60950-1:2005+A1:2009+A2:2013 + National
Differences
AS/NZX 60950-1 (Australia /New Zealand)
12
Minimum is defined as idle, with no ports linked. Maximum is defined as fans high, all ports 100% traffic.
Technical Specifications
ExtremeSwitching and Summit Switches: Hardware Installation Guide
343