6.2 Positioning and dimensioning
The correct dimensioning and positioning of the air sanitizer V1000E is essential for the success
of the sterilization process. Your advisor / dealer will be happy to assist you. Depending on the
intended use, the air delivery rate can be varied between 1000 m³/h and 500 m³/h using a
selector switch (see chapter 6.5 Operation). The volume as well as the UVC dose and thus a
reduction rate change accordingly.
1000m³/h
6,5 mJ/cm²
500m³/h
12,5 mJ/cm²
The V1000E air sanitizer has to be installed in such a way that the air outlet points towards the
main part of the room. For multiple air sanitizer these should be uniformly distributed in the
room. Inlets and outlets should always be free of obstacles within a radius of at least 1m to
ensure good function.
Attention: Correct and efficient positioning needs to be considered and
evaluated in each individual case.
During installation, it should be ensured that the air sanitizer are easily accessible later (e.g. with
aids such as a ladder) and can be cleaned. Furthermore, the accessibility of the switch should
be considered when choosing the installation location. If the switch cannot be reached, it is
advisable to switch the device using an alternative option (e.g. a classic wall switch).