DEPOLOX® 400 M
4. Interfaces
35
EN
400304
UINT16
2
R
Operation mode controller
1 (chlorine)
0
MAN.
1
Auto
2
Controller Aus
3
Adaption running
4
--
5
Controller stop (Yout=0%)
6
Controller freeze
(Yout=Yout)
7
Controller Yout=100%
8
--
9
--
10
--
11
Eco Mode switching
12
Controller standby
400305
400306
400307
400308
400310
UINT32
4
R
Error code chlorine (Ch.1)
0
Zero point calibration
1 = error aktive
1
DPD calibration
1 = error aktive
2
pH7 calibration
1 = error aktive
3
pHX calibration
1 = error aktive
4
Error calibration e.g. ORP (Redox) 1 = error aktive
5
Offset calibration
1 = error aktive
6
--
7
Cell error
1 = error aktive
8
Factory calibration error
1 = error aktive
9
--
10
--
11
Setpoint error
1 = error aktive
12
Limit error
1 = error aktive
13
HOCL error (Cl2++)
1 = error aktive
14
--
15
Overfeed (max. dosing time) 1 = error aktive
16
Auto tune error
1 = error aktive
Modbus
Register
Bit
Type
No.
Byte
Access
Designation
Description
Содержание DEPOLOX