6. Operation
DEPOLOX® 400 M
72
EN
6.7.3 Messages
Cl
2
++
pH measurement is outside
< 6,00 and >8,75
Measurement/Dosiering
check pH
Maximum dosing
time has been
exceeded
The maximum dosing time set for
a control output has been excee-
ded
Check measuring water,
calibration, dosing pump,
chemical storage sensor, sensor
cable, measurement.
Error message
Cause
Remedy
Error message
Cause
Remedy
Cl2 free
Maintenance!
Sensor calibration
Calibration check interval
Time expired
Calibrate the measurement, reset
maintenance interval after cali-
bration and acknowledge mes-
sage.
Fluoride
Maintenance!
Sensor calibration
pH
Maintenance!
Sensor calibration
ORP (Redox)
Maintenance!
Sensor calibration
Cl2 free
Maintenance! Cell
Sensor maintenance
interval expired
Carry out sensor maintenance,
reset maintenance interval and
acknowledge message.
Fluoride
Maintenance! Cell
pH
Maintenance! Cell
ORP (Redox)
Maintenance! Cell
Sample water
Sample water flow rate too low,
dirt filter soiled, sample water
inlet or sample water outlet ball
valve closed, dirt in inlet, flow con-
trol valve or check valve housing.
Open ball valves, clean dirt filter,
remove dirt