![Evoqua DEPOLOX Скачать руководство пользователя страница 33](http://html.mh-extra.com/html/evoqua/depolox/depolox_instruction-manual_2447564033.webp)
DEPOLOX® 400 M
4. Interfaces
33
EN
Modbus Register DEPOLOX® 400 M
IP adress of the device, e.g. 192.168.200.11 Port: 502
Modbus
Register
Bit
Type
No.
Byte
Access
Designation
Description
System information
400001
ASCII
20
R
System name
e.g. "DEPOLOX 400 M"
400011
ASCII
10
R
Software Version
e.g. "V:1.00"
400016
ASCII
10
R
act. date
e.g. "21.02.17"
400021
ASCII
6
R
act. time
e.g. "13:16"
400024
ASCII
16
R
Serial number
(Ch.1) Desinfection - Measurement (DES sensor)
400100
FLOAT
4
R
Measured value
400102
ASCII
10
R
Measured unit
"mg/l"
400107
FLOAT
4
R
Lower range
400109
FLOAT
4
R
Upper range
400111
FLOAT
4
R
Current setpoint
in the measuring range
400113
FLOAT
4
R
Current measuring range/
control value Yout
0.0 - 100.0%
(Ch.2) pH/Fluoride - Measurement
400115
FLOAT
4
R
Measured value
400117
ASCII
10
R
Measured unit
"pH / mg/l"
400122
FLOAT
4
R
Lower range
400124
FLOAT
4
R
Upper range
400126
FLOAT
4
R
Current setpoint
in the measuring range
400128
FLOAT
4
R
Current measuring range/
control value Yout
0.0 - 100.0%
(Ch.3) ORP (Redox) - Measurement
400130
FLOAT
4
R
Measured value
400132
ASCII
10
R
Measured unit
"mV"
400137
FLOAT
4
R
Lower range
400139
FLOAT
4
R
Upper range
400141
4
R
-
400143
4
R
-
(Ch.4) Reserved
400145
400147
400152
400154
400156
400158
Содержание DEPOLOX
Страница 1: ...1 INSTRUCTION MANUAL DEPOLOX 400 M WALLACE TIERNAN DISINFECTION ANALYZER Version 1 14 and later...
Страница 100: ...10 EC Declaration of Conformity and Certificate DEPOLOX 400 M 100 EN 10 EC Declaration of Conformity and Certificate...
Страница 101: ...DEPOLOX 400 M 10 EC Declaration of Conformity and Certificate 101 EN...