EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
85
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
69
L3BypLineApparentPower
Apparent power drawn from the L3 line, mains supply via the bypass
system, quoted with the resolution accuracy of 100 VA.
70
InputPowerFactorBypL1
Input power factor for the L1 input line transmitted by the bypass line,
quoted with the resolution accuracy of a one hundredth
71
InputPowerFactorBypL2
Input power factor for the L2 input line transmitted by the bypass line,
quoted with the resolution accuracy of a one hundredth
72
InputPowerFactorBypL3
Input power factor for the L3 input line transmitted by the bypass line,
quoted with the resolution accuracy of a one hundredth
73
BypFrequency
Power line voltage frequency, bypass system, measured for the L1 line,
quoted with the resolution accuracy of 0.1 Hz.
74-77
Reserved
78
L1OutputLineVoltage
UPS L1 output line voltage, quoted with the resolution accuracy of 1 V
79
L2OutputLineVoltage
UPS L2 output line voltage, quoted with the resolution accuracy of 1 V
80
L3OutputLineVoltage
UPS L3 output line voltage, quoted with the resolution accuracy of 1 V
81
L1OutputLineCurrent
UPS L1 output line current, quoted with the resolution accuracy of 1 A
82
L2OutputLineCurrent
UPS L2 output line current, quoted with the resolution accuracy of 1 A
83
L3OutputLineCurrent
UPS L3 output line current, quoted with the resolution accuracy of 1 A
84
L1OutputActivePower
Active power drawn from the UPS L1 output line, quoted with the
resolution accuracy of 100 W
85
L2OutputActivePower
Active power drawn from the UPS L2 output line, quoted with the
resolution accuracy of 100 W
86
L3OutputActivePower
Active power drawn from the UPS L3 output line, quoted with the
resolution accuracy of 100 W
87
L1OutputApparentPower
Apparent power drawn from the UPS L1 output line, quoted with the
resolution accuracy of 100 VA
88
L2OutputApparentPower
Apparent power drawn from the UPS L2 output line, quoted with the
resolution accuracy of 100 VA
89
L3OutputApparentPower
Apparent power drawn from the UPS L3 output line, quoted with the
resolution accuracy of 100 VA
90
OutpuPowerFactorL1
Output power factor for the L1 line, quoted with the resolution accuracy
of one hundredth
91
OutpuPowerFactorL2
Output power factor for the L2 line, quoted with the resolution accuracy
of one hundredth
92
OutpuPowerFactorL3
Output power factor for the L3 line, quoted with the resolution accuracy
of one hundredth
93
L1Load
Percentage load for active power, L1 phase, quoted with the resolution
accuracy of one per cent.
94
L2Load
Percentage load for active power, L2 phase, quoted with the resolution
accuracy of one per cent.
95
L3Load
Percentage load for active power, L3 phase, quoted with the resolution
accuracy of one per cent.
96
OutputVoltageFrequency
UPS output voltage frequency, quoted with the resolution accuracy of 0.1
Hz
97-101
Reserved
102
CheckingWork
UPS mode of operation status
103
L1PhaseOutputVoltage
L1 phase output voltage for the UPS in the inverter-based mode, quoted
with the resolution accuracy of 1V.
104
L2PhaseOutputVoltage
L2 phase output voltage for the UPS in the inverter-based mode, quoted
with the resolution accuracy of 1V.
105
L3PhaseOutputVoltage
L3 phase output voltage for the UPS in the inverter-based mode, quoted
with the resolution accuracy of 1V.
106
UpperVoltageValue
Parameter/word used for configuration of the upper voltage value for the
bypass system to ensure correct supply parameters, quoted with the
resolution accuracy of 1V.
107
LowerVoltageValue
Parameter/word used for configuration of the lower voltage value for the
bypass system to ensure correct supply parameters, quoted with the
resolution accuracy of 1V.
108
LowerVoltageFrequencyValue
Parameter/word used for configuration of the lower voltage frequency
value for the bypass system to ensure correct supply parameters, quoted
with the resolution accuracy of 1 Hz.
109
UpperVoltageFrequencyValue
Parameter/word used for configuration of the upper voltage frequency
value for the bypass system to ensure correct supply parameters, quoted
with the resolution accuracy of 1 Hz.
110
OverloadStop
Binary value, quoted in percentage of the maximum UPS output power,
below which the unit stops indicating output overload.
and continues operation according to the configuration
111
AdresJednRown
Setting the address of the power supply in case of parallel or redundant
112
MinLiczJednPR
Determination of the required minimum number of units in the system
113-114
Reserved
115
ModbusAdres
Setting the device address in the MODBUS network