![Ever W/PGRLTO-3310K0/00 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/ever/w-pgrlto-3310k0-00/w-pgrlto-3310k0-00_instruction-manual_2442563036.webp)
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
36
View of the
screen:
EVENTS Sub-menu
The EVENTS Sub-menu uses a single screen which displays information about the
events that have occurred. The event register has a capacity to show up to 40
events. After the register becomes full, each new event is recorded by overwriting the
oldest event in the list. To exit this screen, press the
ESC
key.
Description: Information about the event history
Type: Readout
Parameters: The following information is displayed on the panel in the following
sequence:
- the event record number (1-40)
- date of the event (<month-day>)
- time (hours:minutes:seconds)
- type of event (M, A, i)
M
– mode of operation,
A
– alarm,
i
- message
– short additional information as shown in Table 4
Events correspond to the messages shown on the display, where:
“On” denotes the
occurrence of an event, and “Off” denotes the disappearance of the event’s cause.
Table 4. List of event messages
TYPE
Short description
Mo
de
of
o
per
a
ti
on
M INIT
M NORMAL
M HYBRID
M BATTERY
M ECO
M STOP
M WATCH
M STANDBY
M BYPASS
M EMERGENCY
A
la
rm
a
le
rt
s
A ShortCircuit
A Overload
A RecOverTemp
A InvOverTemp
A BatteryFail
A EPO
A RecInternalError
A InvInternalError
A PO Fault
Mes
s
a
ges
i BatteryChargeOn / BatteryChargeOff
i OverloadOn / OverloadOff
i RecOverTempOn / RecOverTempOff
i InvOverTempOn / InvOverTempOff
i MinChargeWaitOn / MinChargeWaitOff
i LowBatteryOn / LowBatteryOff
i SerwisOn / SerwisOff
Содержание W/PGRLTO-3310K0/00
Страница 1: ......