TECHNICAL PARAMETERS
Table 9. Technical parameters
PARAMETERS \ TYPE
POWERLINE GREEN 33 LITE
Model 10k
Model 15k
Model 20k
Model 30k
Model 40k
Model 50k
Model 60k
Part number
W/PGRLTO
-3310K0/00
W/PGRLTO
-3315K0/00
W/PGRLTO
-3320K0/00
W/PGRLTO
-3330K0/00
W/PGRLTO
-3340K0/00
W/PGRLTO
-3350K0/00
W/PGRLTO
-3360K0/00
Output Power (Apparent / Active)
1)
10 kVA
10 kW
15 kVA
12 kW
20 kVA
16 kW
30 kVA
24 kW
40 kVA
32 kW
50 kVA
40 kW
60 kVA
45 kW
GENERAL DATA AND ENVIRONMENTAL
Topology
VFI (on-line, VFI-SS-111)
Number of phases (in/out)
3 / 3
Housing Type
Tower
Max efficiency (double conversion mode)
< 94%
Max efficiency (ECO mode)
> 98%
Operating temperature
2)
0 ÷ +40 °C
Storage temperature
0 ÷ +40 °C
Relative humidity during operation
< 95% (non-condensing)
Relative humidity during storage
< 95% (non-condensing)
Operating elevation
3)
< 1000 m
Protection level
IP20
Environment of installation
Separate rooms with low contamination level
Cooling
Forced, internal fans
Temperature of the cooling air
< 20°C
Quantity of heat released for nominal
work conditions
< 2600
BTU / h
< 3100
BTU / h
< 4100
BTU / h
< 6200
BTU / h
< 8100
BTU / h
< 10300
BTU / h
< 11600
BTU / h
INPUT
Nominal input voltage
3 x 400 V AC
Input voltage range and tolerance
173 ÷ 485 V AC ± 2%
Rated current
16 A
19 A
25 A
37 A
50 A
62 A
70 A
Input voltage rated frequency
50 Hz
Input voltage frequency range and
tolerance
45 ÷ 55 Hz ± 1 Hz
Input Power Factor
> 0,99
Input current distortion (THDi)
< 2%
Reactive power compensation
0 var
Reactive power factor tg
ϕ
< 0,4