EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
40
The RELAYS Sub-menu
The unit is fitted with a total of four non-voltage outputs that can be programmed by
the user. The actuators in this case are relays. The relay contacts have the following
parameters: 1 A / 250 V AC).
An event that can potentially occur within the UPS system could then be assigned to
each of those relays. In order to configure the available outputs, please go to the
RELAYS sub-menu. This sub-menu uses two screens which show all the relays and
the events that have been assigned to them:
Accepting the selection of a particular relay by pressing the
key takes you to the
editing option for this command.
The following settings shown in
Fig. 6
are available.
Table. 6. List of relay settings
Setting
Description
Off
Relay inactive
M NORMAL
Modes of operation
M BYPASS
M BATTERY
M STANDBY
M ECO
M EMERGENCY
Charging
Messages
Overload
RecOverTemp
InvOverTemp
MinChargeWait
LowBattery
Service
Bypass
BypOutOfRange
MainsOutOfRange
EPO
Alerts
To switch between individual settings, press the ▲▼ keys. Confirm by pressing the
key. To abort introducing the changes. press the
ESC
key.