![Ever W/PGRLTO-3310K0/00 Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/ever/w-pgrlto-3310k0-00/w-pgrlto-3310k0-00_instruction-manual_2442563079.webp)
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
79
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
PARAMETERS \ TYPE
POWERLINE GREEN 33 LITE
Model 10k Model 15k Model 20k Model 30k Model 40k Model 50k Model 60k
Output Power (Apparent / Active)
1)
10 kVA
10 kW
15 kVA
12 kW
20 kVA
16 kW
30 kVA
24 kW
40 kVA
32 kW
50 kVA
40 kW
60 kVA
45 kW
OUTPUT
Nominal output voltage
3 x 400 V AC
Output voltage range and tolerance - normal
mode
3 x (380 ÷ 415) V AC ± 2%, configurable
Output voltage range and tolerance - battery
mode
3 x (380 ÷ 415) V AC ± 2%, configurable
Rated current
15 A
22 A
29 A
44 A
58 A
73 A
87 A
Shape of output voltage (battery mode / normal
mode)
sine-wave / sine-wave
Output voltage rated frequency
50 Hz
Output frequency range and tolerance
– mains
operation mode
Synchronously
Output frequency range and tolerance
– battery
mode
50 Hz ± 0,1 Hz
Output voltage regulation
< 1%
Output voltage distortion THDu
< 0,4% for Pmax (line)
< 5% (non-line by PN-EN 62040-3)
Crest Factor CF
7:1
5:1
4:1
5:1
4:1
3:1
3:1
Transfer time to battery mode
0 ms
Transfer time to normal mode
0 ms
Overload capability
4)
130% - 10 min
160% - 1 min
300% - 100 ms
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
12 V / 7 Ah VRLA or 12 V / 9 Ah VRLA
Number of internal batteries
64 (2 x 32)
Maximum overall internal batteries capacity
9 Ah
External battery modules (EBM)
Yes
Maximum overall external batteries capacity
5)
200 Ah
400 Ah
500 Ah
Backup time
– internal batteries ( 100 % / 80 % /
50 % Pmax)
Depends on the type and number of batteries
Backup time
– internal bat EBM
(100%/80%/50%Pmax)
Depends on the type and number of batteries
Nominal voltage DC circuit
± 384 V DC
Internal batteries maximum charging time
– after
discharging at 80 % Pmax
Depends on the type and number of batteries
Maximum charging current
5)
10 A
20 A
25 A
MECHANICAL SPECIFICATIONS
Dimensions (H x W x D)
895 x 435 x 855 mm
1150 x 485 x 855 mm
1150 x 485 x 855 mm
Net Weight
6)
265 kg
320 kg
340 kg
Gross Weight
6)
280 kg
335 kg
355 kg
Transport Dimensions (H x W x D)
1045 x 800 x 1200 mm
1300 x 800 x 1200 mm
1300 x 800 x 1200 mm
Position in which devices transported
Vertical
PROTECT
Input over current protection
Short-circuit / Overload
– Three-pole
breaker
B32 A / 400 V AC
Short-circuit / Overload
– Three-pole breaker
B63 A / 400 V AC
Short-circuit / Overload
– Three-pole breaker
B100 A / 400 V AC
Surge Protection
Bypass line working
– short-circuit and overload protection
Output over current protection
Inverter working
– electronic short-circuit and overload protection
DC over current (internal batteries)
2 x 30 A / 440 V DC
cylindrical 10 x 38
2 x 63 A / 440 V DC
cylindrical 22 x 58
2 x 100 A / 440 V DC
cylindrical 22 x 58
DC over current (external battery input)
2 x 30 A / 440 V DC
cylindrical
10 x 38
(optional equipment)
2 x 63 A / 440 V DC
cylindrical
22 x 58
(optional equipment)
2 x 100 A / 440 V DC
cylindrical
22 x 58
(optional equipment)
Содержание W/PGRLTO-3310K0/00
Страница 1: ......