EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
Type 01 2016-10-27 12:12
Technical Service, tel.: +48 61 6500 400
www.ever.eu
28
CONFIGURATION 2/7
Description: Parameters of the UPS unit
Type: Readout/Saving
Parameters:
UUppTresh
– Setting the maximum (upper) voltage limit for the BYPASS
line
ULowTresh
– Setting the minimum (lower) voltage limit for the BYPASS line
fLowTresh
– Setting the minimum (lower) frequency limit for the BYPASS
line
View of the
screen:
CONFIGURATION 3/7
Description: Parameters of the UPS unit
Type: Readout/Saving
Parameters:
fUppTresh
– Setting the maximum (upper) frequency limit for the BYPASS
line
STB Delay
– Setting the delay when switching to the STANDBY mode in
case of overriding switching by the user. When management
software is used, this delay should be more than the time
needed to switch off the management system.
STB Charge
– Setting the minimum battery charging level that needs to be
achieved to enable the UPS unit to start following batteries’
discharge, after voltage in the mains becomes available again
(and battery charging resumes)
View of the
screen:
CONFIGURATION 4/7
Description: Parameters of the UPS unit
Type: Readout/Saving
Parameters:
OvlClrTresh
– Permitted load at which the UPS unit stops indicating
overload (alert).
Protocol
– Selection of the communication protocol: EVER or MODBUS.
MODBUSAdres
– Selection of the communication protocol.