![Ever W/PGRLTO-3310K0/00 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/ever/w-pgrlto-3310k0-00/w-pgrlto-3310k0-00_instruction-manual_2442563059.webp)
EVER POWERLINE GREEN 33 LITE UPS Range Operating Manual
59
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-10-27 12:12 Type 01
ADDITIONAL FUNCTIONALITIES OF THE UPS UNIT
ADDITIONAL FUNCTIONAL ELEMENTS
Manual bypass function
The UPS unit may be equipped (optionally) with a manual switch for the BYPASS
line (
Fig. 13
). This switch enables direct switching over of the BYPASS line to
connect with the UPS output terminals, thus bypassing the UPS unit’s blocks.
Figure 13: Manual BYPASS line switch
Switch in the UPS position
– normal UPS unit operation.
Switch in the BYPASS position
– the BYPASS lines become switched to connect with
the output terminals. This switching can be completed at any time. However, this
switching does not happen without an interruption. The certain time delay is a direct
result of a mechanical switching of terminals.
Control input and DC power supply ports
The EVER POWERLINE GREEN 33 LITE power supply unit equipped with four
control input ports and a DC power supply connection (non-stabilised 1 A / 12 V DC
protected by a PTC resettable fuse)
–
Fig. 14
. Those control input ports allow the
possibility of remote setting/configuring (unanimously assigned)
of the UPS unit’s
functionalities. Individual contacts are assigned with functions listed in
Table 7.