Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
PC63
Probe active for automatic conversion
0: External temperature
1: Coil 1 temperature
2: Room/return temperature
2
0
2
IS-R
C63
FANS
PF02
Fan regulation differential
5.0
0.0
30.0
°C
IS-F
PF01=0 or 1
F02
PF06
Modulating or manual step regulation value
05:00
01:00
100.00
%
IS-F
F06
Binding if digital
fans
PF21
Supply fan forced setpoint 1
33.0
-999.0
3276.0
IS-F
F21
PF22
Supply fan forced setpoint 2
66.0
-999.0
3276.0
IS-F
F22
PF23
Supply fan forced setpoint 3
100.0
-999.0
3276.0
IS-F
F23
PF28
Return fan percentage delta
42.0
PF52
PF53
Pa/m
3
min
IS-F
F34
PF29
Return fan step delta
50.0
PF52
PF53
Pa/m
3
min
IS-F
F35
PF33
Return fan forced setpoint 1
100
PF52
PF53
Pa/ m
3
h*10 IS-F
F33
PF34
Return fan forced setpoint 2
250
PF52
PF53
Pa/ m
3
h*10 IS-F
F34
PF35
Return fan forced setpoint 3
300
PF52
PF53
Pa/ m
3
h*10 IS-F
F35
PF36
Type of forced setpoint:
0: No setpoint
1: Setpoint 1
2: Setpoint 2
3: Setpoint 3
0
0
3
IS-F
F36
PF41
Constant supply pressure/flow neutral zone
3.0
1.0
999.0
Pa/m
3
min
IS-F
F41
PF42
Constant return pressure/flow setpoint
3.0
1.0
999.0
Pa/m
3
min
IS-F
F43
PF44
Constant pressure/flow fan speed increase/decrease
time
5
1
100
Sec
IS-F
F44
PF45
Constant pressure/flow fan speed increase/decrease
percentage
01:00
00:00
100.00
%
IS-F
F45
PF48
Supply fan flow coefficient
72
0
9999
IS-F
F48
PF56
Return fan flow coefficient
72
0
9999
IS-F
F56
PF58
Booster time if enabled by key
10
0
255
Min
IS-F
F58
PF59
Comfort
band
constant
supply
pressure/flow
setpoint
35.0
PF50
PF51
Pa/m
3
min
IS-F
F59
PF60
Economy
band
constant
supply
pressure/flow
setpoint
35.0
PF50
PF51
Pa/m
3
min
IS-F
F60
PF61
Night
band
constant
supply
pressure/flow
setpoint
35.0
PF50
PF51
Pa/m
3
min
IS-F
F61
PF62
Comfort
band
constant
return
pressure/flow
setpoint
35.0
PF52
PF53
Pa/m
3
min
IS-F
F62
PF63
Economy
band
constant
return
pressure/flow
setpoint
35.0
PF52
PF53
Pa/m
3
min
IS-F
F63
PF64
Night
band
constant
return
pressure/flow
setpoint
35.0
PF52
PF53
Pa/m
3
min
IS-F
F64
COILS
Pb01
Proportional band for regulating the cooling and
heating valves
10.0
0.0
20.0
°C
IS-B
b01