EVCO S.p.A.
c-pro 3 OEM HRV | Application handbook ver. 4.0 | Code 144CP3OHE404
page 64 of 138
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
Pb02
Integral time for regulating the cooling and heating
valves
0
0
999
Sec
IS-B
If Pb02=0 integral
action not present
b02
Pb03
Neutral zone for temperature regulation
4.0
0.0
20.0
°C
IS-B
b03
Pb05
Maximum deviation for the floating supply setpoint
calculation
3.0
0.0
20.0
°C
IS-B
If Pb05=0 function
not enabled
b05
Pb06
Proportional band for the calculation of the floating
supply setpoint
5.0
0.0
20.0
°C
IS-B
b06
Pb21
Second complete hot neutral zone for two heating
coils
12.0
0.0
20.0
°C
IS-B
b21
Pb22
Second differential for 2 heating coils
3.0
0.0
10.0
°C
IS-B
b22
Pb23
Entire neutral zone for mid-season control
4.0
0.0
20.0
°C
IS-B
b23
Pb24
Differential or mid-season control
10.0
0.0
10.0
°C
IS-B
b24
Pb30
Enable supply limitation
0: Disabled
1: Heating
2: Cooling
3: Enabled
3
0
3
IS-B
b30
Pb31
Cooling limitation setpoint
10.0
-15.0
70.0
°C
IS-B
b31
Pb32
Cooling limitation differential
5.0
0.0
30.0
°C
IS-B
b32
Pb33
Cooling limitation minimum value
0.0
0.0
100.0
%
IS-B
b33
Pb34
Heating limitation setpoint
30.0
-15.0
70.0
°C
IS-B
b34
Pb35
Heating limitation differential
5.0
0.0
30.0
°C
IS-B
b35
Pb36
Heating limitation minimum value
0.0
0.0
100.0
%
IS-B
b36
HUMIDIFIER
PU02
Neutral zone for humidity regulation
6
0
100
%
IS-U
U02
PU03
Humidity regulation differential
10
0
100
%
IS-U
U03
PU04
Integral time for regulating dehumidification (on a
cooling coil)
0
0
999
Sec
IS-U
If PU04=0 integral
action not present
U04
PU17
Winter dehumidification enabling
YES (1)
NO (0)
YES (1)
IS-U
U17
PU18
Winter dehumidification setpoint
55
0
100
%
UT
U18
PU19
Winter dehumidification neutral zone
6
0
100
%
IS-U
U19
PU20
Winter dehumidification differential
10
0
100
%
IS-U
U20
PU21
Winter dehumidification integral time
0
0
999
Sec
IS-U
If PU04=0 integral
action not present
U21
PU22
Setpoint for maximum damper opening in winter
dehumidification
50.00
00:00
100.00
%
IS-U
U22
PU23
Differential for maximum damper opening in winter
dehumidification
20:00
00:00
100.00
%
IS-U
U23
PU24
Mixing chamber damper control in winter dehumidifi-
cation:
0: Winter dehumidification only
1: Regulation only
2: Greater of the two
3: Average of the two
1
0
3
IS-U
U24