EVCO S.p.A.
c-pro 3 OEM HRV | Application handbook ver. 4.0 | Code 144CP3OHE404
page 114 of 138
HEATING
8.12.3
Modulating direct expansion coil
To use the modulating regulation, set parameter
PG07=3
.
COOLING
HEATING
By setting parameter PH59 of the polarity of the analog output of the direct expansion battery to Custom, it is possible to manage the direct expansion battery accord-
ing to the logic defined by the graphs below. To use this function correctly, the following parameters must also be set:
PE16:
Minimum output value in cooling for custom regulation
PE17:
Maximum output value in cooling for custom regulation
PE18:
Minimum output value in heating for custom regulation
PE19:
Maximum output value in heating for custom regulation
Pb01/2
SETH: Winter setpoint
Return T.
NZ Pb03
2
Pb01: Diff
1 STEP
SETC: Summer setpoint
0%
Return T.
Pb01: Diff
100%
NZ Pb03
SETH: Winter setpoint
0%
Return T.
Pb01: Diff
100%
NZ Pb03