EVCO S.p.A.
c-pro 3 OEM HRV | Application handbook ver. 4.0 | Code 144CP3OHE404
page 71 of 138
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
Pb43
Pre-heating modulation percentage variation
5.0
1.0
50.0
%
CO-B
b43
Pb44
Coil 1 run time with 3-point check
20
0
3600
Sec
CO-B
b44
Pb45
Extra time for coil 1 limit switch with 3-point check
10
0
600
Sec
CO-B
b45
Pb46
Coil 2 run time with 3-point check
20
0
3600
Sec
CO-B
b46
Pb47
Extra time for coil 2 limit switch with 3-point check
10
0
600
Sec
CO-B
b47
Pb48
Pre-heating coil run time with 3-point check
20
0
3600
Sec
CO-B
b48
Pb49
Extra time for pre-heating coil limit switch with 3-
point check
10
0
600
Sec
CO-B
b49
Pb50
Minimum variation for coil relay activation with 3-
point check
0.00
0.00
100.00
%
CO-B
b50
Pb51
Re-heating coil run time with 3-point check
20
0
3600
Sec
CO-B
b51
Pb52
Extra time re-heating coil limit switch with 3-point
check
10
0
600
Sec
CO-B
b52
DIRECT EXPANSION
PE01
Minimum compressor switch-off time
180
0
9999
Sec
CO-DE
E01
PE02
Minimum compressor switch-on time
60
0
9999
Sec
CO-DE
E02
PE03
Minimum time between two switch-ons of the same
compressor
300
0
9999
Sec
CO-DE
E03
PE04
Switch off time between two compressors
20
0
999
Sec
CO-DE
E04
PE05
Switch on time between two compressors
10
0
9999
Sec
CO-DE
E05
PE06
Defrost interval
8
1
99
H
CO-DE
E06
PE07
Type of defrost
0: Cycle reversal
1: Compressor stoppage
0
0
1
CO-DE
E07
PE08
End of defrost setpoint
10.0
PE12
20.0
°C
CO-DE
E08
PE09
Defrosting maximum time
30
1
99
Min
CO-DE
E09
PE10
Dripping duration
2
0
15
Min
CO-DE
E10
PE11
Counting type defrost interval
0: Unit ON
1: Compressor ON
2: Defrost.T < PE12 threshold
2
0
2
CO-DE
E11
PE12
Start defrost count threshold
8.0
0.0
PE08
°C
CO-DE
E12
PE13
Type of compressor rotation
0: Fixed sequence
1: Hours + startings
0
0
1
CO-DE
E13
PE14
Wear: based on hours
1
0
50
CO-DE
E14
PE15
Wear: based on peaks
1
0
50
CO-DE
E15
PE16
Minimum output value in cooling for custom regula-
tion
2.20
0.00
PE17
V
CO-DE
E16
PE17
Maximum output value in cooling for custom regula-
tion
8.50
PE16
10.00
V
CO-DE
E17
PE18
Minimum output value in heating for custom regula-
tion
1.50
0.00
PE19
V
CO-DE
E18
PE19
Maximum output value in heating for custom regula-
tion
8.50
PE18
10.00
V
CO-DE
E19
HUMIDIFIER