www.evaelektromekanik.com

CABLE CONNECTION CUBICLE 

36kV

MET

AL

 ENCL

OSED MODULAR S

WIT

CHGEARS 

(MMMH) USER GUIDE

Assembly, Operating and Maintenance Instructions

Содержание eva-36-CR

Страница 1: ...www evaelektromekanik com CABLE CONNECTION CUBICLE 36kV METAL ENCLOSED MODULAR SWITCHGEARS MMMH USER GUIDE Assembly Operating and Maintenance Instructions...

Страница 2: ...90 312 811 27 27 Fax 90 312 811 27 28 www evaelektromekanik com All rights reserved Any part of this catalogue can not be copied without the permission of the right holder It can only be copied and au...

Страница 3: ...THE MAIN GROUNDING SYSTEM OF THE FACILITY 9 3 8 PASSAGES OF AUXILIARY SERVICE AND CONTROL CABLES FROM CUBICLE TO ANOTHER 10 3 9 CONNECTION OF MV CABLES 11 3 10 MATTERS TO BE CONSIDERED AGAINST INTERN...

Страница 4: ...e related quality control processes to all the modulars the products will be ready for delivery and installation 1 1 GENERAL SECTIONS eva 36 CR SWITCHING SYSTEM IS FULLY COMPLIANT WITH TS EN IEC 62271...

Страница 5: ...on Cable Connection and Main Busbar IAC A FL 16kA 1sec Protection Level TS 3033 EN 60529 IP3X Applied Standard TS EN IEC 62271 1 TS EN IEC 62271 200 Height mm 2250 Width mm 750 Depth mm 1400 1 3 KARAK...

Страница 6: ...les can be carried either way as shown in the the pictures below In addition forklift is usually used to unload the cubicles from the truck and transport them to the assembly site 2 1 TRANSPORTATING W...

Страница 7: ...ON 3 2 MATERIALS LIST SENT WITH THE CUBICLE Tools Dimensions Quantity Open End Wrench 10 2 Pcs Open End Wrench 13 2 Pcs Open End Wrench 15 1 Pcs Open End Wrench 17 1 Pcs Open End Wrench 19 1 Pcs Open...

Страница 8: ...t inside the Building 3 3 CUBICLE S PLACEMENT Base holes that enable the cubicles to be fixed to the ground are provided as shown in the below picture Fix the cubicles to the ground by using M10 steel...

Страница 9: ...el peg or an iron dowel should be used Then the holes to be fixed with M10x50 bolts MV Cable Entry Point Pull the lifting hooks upwards See below pictures Bring the cubicles to the settlement area by...

Страница 10: ...ighten the bolts with 50Nm torque 3 Wipe the insulators and solid insulation materials with a dry clean cloth 4 Assemble the upper cover plate IMPORTANT WARNING If the surface on which the cubicles wi...

Страница 11: ...s main grounding system use the grounding busbar located in the cable connection compartment of the cubicles See Picture 4 Any of the cubicles at the beginning or at the end of the cubicle s array ca...

Страница 12: ...xt cubicle See the left picture 6 NOTE The connection between cubicle to another is made by combining the cable entry sockets that contain the electrical interlock and AC DC cables to each other NOTE...

Страница 13: ...les from passing through them See picture 8 1 Open the cubicle s cable connection compartment door 2 Mount the cable terminal caps internal type on the MV cable terminals in accordance with the relate...

Страница 14: ...is any unusual object inside the cubicle and take it out 3 Check that there is at least 100 mm gap between the cubicles back and the building s wall and that there is no objects in between 4 Check wh...

Страница 15: ...AINTENANCE AND INSTALLATION Tools Dimensions Quantity Dirt Chemical Solution Clean Cloth Open End Wrench 10 13 15 17 19 24 2 Pcs Torque Wrench 1 Pcs Socket Wrench 1 Pcs Socket 10 13 15 17 19 24 1 Pcs...